Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 30, 2020, 08:04 AM
  • 05 2634_05 2662 _10302020_000719.mp4

Date
10/30/2020
W/O
855371
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z01146
PipeID
P26135
Time
1:04 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8142
Sewer Name
PALOS VERDES NORTH SLOPE REPLACEMENT TRUNK, SECT 1A
City
TORRANCE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
35
Purpose
Routine Assessment
Project
RFIR_WO_855371_TV05087_OCT2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
05 2634
Downstream MH
05 2662
Dir. of Survey
Downstream
Length Surveyed
45.1 ft.
Total Length
45.1 ft.
Structural Index
2
Structural Quick
2800
Structural Rating
16
O&M Index
2
O&M Quick
2800
O&M Rating
16
Overall Index
2
Overall Quick
Overall Rating
32
Pipe schematic from manhole 05 2634 to 05 2662
MH: 05 2634MH: 05 2662downstream0 ft. AMH - Upstream Manhole, Survey Begins - 05 26340 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start43 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish43 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish45.1 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE45.1 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE45.1 ft. AMH - Downstream Manhole, Survey Ends - 05 2662

Observations (10)

DistanceCodeObservation
45.1MGOCONN @ MH 9 O'CLOCK/ACTIVE
2DAGS
0AMH05 2634
0MWL
0MWM
45.1MGOCONN @ MH 3 O'CLOCK/ACTIVE
43DAGS
2SSS
43SSS
45.1AMH05 2662

Properties (8)

additional_info
630102900075P1
custom_field_three
RFIR NO SEVERE DEFECTS
custom_field_two
3
customer
1
datetime
2020-10-30T01:04:07-07:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
40008