Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 30, 2020, 09:41 AM
  • 05 2658_05 2657 _10302020_014701.mp4

Date
10/30/2020
W/O
855371
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z01146
PipeID
P26130
Time
2:41 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8142
Sewer Name
PALOS VERDES NORTH SLOPE REPLACEMENT TRUNK, SECT 1A
City
TORRANCE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
35
Purpose
Routine Assessment
Project
RFIR_WO_855371_TV05087_OCT2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
05 2658
Downstream MH
05 2657
Dir. of Survey
Downstream
Length Surveyed
280.8 ft.
Total Length
280.8 ft.
Structural Index
2
Structural Quick
2J00
Structural Rating
110
O&M Index
2
O&M Quick
2J00
O&M Rating
110
Overall Index
2
Overall Quick
Overall Rating
220
Pipe schematic from manhole 05 2658 to 05 2657
MH: 05 2658MH: 05 2657downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 26582 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start179.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN278 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish278 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish280.8 ft. AMH - Downstream Manhole, Survey Ends - 05 2657

Observations (9)

DistanceCodeObservation
2SSS
179.4TFOPEN
0MWL
280.8AMH05 2657
0MWM
0AMH05 2658
278DAGS
278SSS
2DAGS

Properties (8)

additional_info
630102900075P1
custom_field_three
RFIR NO SEVERE DEFECTS
custom_field_two
3
customer
1
datetime
2020-10-30T02:41:30-07:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
40008