Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 27, 2020, 09:05 AM
  • 29 0544_29 0543_10272020_012156.mp4

Date
10/27/2020
W/O
855105
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z01090
PipeID
P24652
Time
2:05 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8138
Sewer Name
ALAMITOS PUMPING PLANT SEWER
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
04
Purpose
Routine Assessment
Project
RFIR_WO_855105_TV29104_OCT2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0544
Downstream MH
29 0543
Dir. of Survey
Downstream
Length Surveyed
299.6 ft.
Total Length
299.6 ft.
Structural Index
3
Structural Quick
433K
Structural Rating
310
O&M Index
2
O&M Quick
2L00
O&M Rating
126
Overall Index
2
Overall Quick
Overall Rating
436
Pipe schematic from manhole 29 0544 to 29 0543
MH: 29 0544MH: 29 0543downstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 29 05440 ft. MGO - General Observation - ROACHES @ MH2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start33.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN41.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN83.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN98 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN101.9 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN105.4 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES126.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES146 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6" - FRACTURED CONN/OPEN151.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN188.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES190.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN192.6 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6" - 55% GREASE-LATERAL/OPEN216.8 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6" - BROKEN CONN/ACTIVE249.7 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6" - 40% GREASE-LATERAL/OPEN297 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish297 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish299 ft. MGO - General Observation - ROACHES @ MH299.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish299.6 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE299.6 ft. AMH - Downstream Manhole, Survey Ends - 29 0543

Observation photos (5)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN

    101.9 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    105.4 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    126.1 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    188.7 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (27)

DistanceCodeObservation
0MWM
0MWL
216.8TFDBROKEN CONN/ACTIVE
0AMH29 0544
33.3TFOPEN
2CM
41.8TFOPEN
83.7TFOPEN
2SSS
297SSS
0MGOROACHES @ MH
190.6TFOPEN
299.5CM
299.6MGOCONN @ MH 9 O'CLOCK/ACTIVE
297DAGS
101.9TBOPEN
105.4FM
2DAGS
188.7FM
126.1FM
249.7TFD40% GREASE-LATERAL/OPEN
151.9TFOPEN
299MGOROACHES @ MH
98TFOPEN
192.6TFD55% GREASE-LATERAL/OPEN
299.6AMH29 0543
146TFDFRACTURED CONN/OPEN

Properties (7)

additional_info
6301026200075P2
custom_field_three
MULTIPLE CRACKS/FRACTURE'S
custom_field_two
2
customer
1
datetime
2020-10-27T02:05:26-07:00
documentation
PROPIPE
is_lateral_inspection
false