05 2093_O5 HAWTHORNE_4182019_014655.mp4
2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE UNDER MAG COAT
2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start
2 ft. - General Observation - 98% MAG COAT START
12.5 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG UNDER MAG COAT
21.3 ft. - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE
48 ft. - Surface Aggregate Visible, from 09 to 11 o'clock, within 8 inches of joint: NO - SEVERE AGG
76.6 ft. - Surface Aggregate Visible, from 08 to 11 o'clock, within 8 inches of joint: NO - SEVCERE VAGG
86.4 ft. - Surface Aggregate Visible, from 01 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG
163.4 ft. - Surface Aggregate Projecting, from 09 to 11 o'clock, within 8 inches of joint: NO - SEVERE AGG
521 ft. - Surface Aggregate Projecting, from 01 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG
| Distance | Code | Observation |
|---|---|---|
| 86.4 | SAV | SEVERE AGG |
| 770.1 | SSS | BLISTERING PEELING CONCRETE |
| 48 | SAV | SEVERE AGG |
| 770.1 | MGO | 90 90% MAG COAT FINISH |
| 770.1 | SAV | SEVERE AGG |
| 21.3 | SSS | BLISTERING PEELING CONCRETE |
| 0 | MWM | — |
| 2 | SSS | BLISTERING PEELING CONCRETE UNDER MAG COAT |
| 76.6 | SAV | SEVCERE VAGG |
| 0 | MWL | — |
| 770.1 | DAGS | — |
| 770.7 | AMH | 2:30AM |
| 163.4 | SAP | SEVERE AGG |
| 12.5 | SAV | SEVERE AGG UNDER MAG COAT |
| 0 | AMH | 1:45AM |
| 521 | SAP | SEVERE AGG |
| 2 | DAGS | — |
| 2 | MGO | 98% MAG COAT START |
| 770.1 | MGO | Conn. @ Mh, 2 O' Clock. Active |
| 164.7 | MGO | 90% MAG COAT START |