Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 12, 2020, 11:18 AM
  • 16 0339_16 0338 _11122020_033701.mp4

Date
11/12/2020
W/O
855315
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00665
PipeID
P13390
Time
3:18 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8205
Sewer Name
SAN MARINO OUTFALL TRUNK
City
SAN MARINO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
17
Purpose
Routine Assessment
Project
RFIR_WO_855315_TV16060_OCT2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
16 in.
Width
16 in.
Upstream MH
16 0339
Downstream MH
16 0338
Dir. of Survey
Downstream
Length Surveyed
297 ft.
Total Length
297 ft.
Structural Index
4
Structural Quick
4K00
Structural Rating
232
O&M Index
2
O&M Quick
2K1A
O&M Rating
131
Overall Index
3
Overall Quick
Overall Rating
363
Pipe schematic from manhole 16 0339 to 16 0338
MH: 16 0339MH: 16 0338downstream0 ft. AMH - Upstream Manhole, Survey Begins - 16 03390 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area2.5 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2.5 ft. RFB - Roots Fine Barrell, at 09 o'clock13.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"37.4 ft. RFJ - Roots Fine Joint, at 04 o'clock, within 8 inches of joint: YES62.9 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start82.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"113.5 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish133.8 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6"150.5 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 6"153.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"224.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"266 ft. TBI - Tap Break-In Intruding, at 01 o'clock, -, -, within 8 inches of joint: YES, 6", 1"288.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"293.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish293.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish294.6 ft. MGO - General Observation - HOLE IN INVERT296.5 ft. MGO - General Observation - CONNECTION AT MH, 9 O'CLOCK297 ft. AMH - Downstream Manhole, Survey Ends - 16 0338

Observation photos (9)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.5 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.5 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Roots Fine Barrell, at 09 o'clock

    2.5 ft. - Roots Fine Barrell, at 09 o'clock

  • Roots Fine Joint, at 04 o'clock, within 8 inches of joint: YES

    37.4 ft. - Roots Fine Joint, at 04 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    62.9 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6"

    133.8 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 6"

    150.5 ft. - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Break-In Intruding, at 01 o'clock, -, -, within 8 inches of joint: YES, 6", 1"

    266 ft. - Tap Break-In Intruding, at 01 o'clock, -, -, within 8 inches of joint: YES, 6", 1"

  • General Observation - HOLE IN INVERT

    294.6 ft. - General Observation - HOLE IN INVERT

Observations (22)

DistanceCodeObservation
0AMH16 0339
0MWM
2.5FM
113.5RFJ
37.4RFJ
0MWL
266TBI
296.5MGOCONNECTION AT MH, 9 O'CLOCK
297AMH16 0338
293.6DAGS
62.9RFJ
2.5DAGS
153.3TFC
294.6MGOHOLE IN INVERT
2.5RFB
82.4TFC
133.8TB
293.6FM
150.5TB
288.8TFC
13.9TFC
224.9TFC

Properties (6)

custom_field_three
MULTIPLE FRACTURES
custom_field_two
3
customer
1
datetime
2020-11-12T03:18:09-08:00
documentation
PRO PIPE
is_lateral_inspection
false