Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 18, 2020, 03:53 PM
  • 16 0336_16 0335_11182020_082617.mp4

Date
11/18/2020
W/O
855315
Weather
Dry
Operator/Surveyor
N.Zahreddine
Sewer ID
Z00665
PipeID
P13387
Time
7:53 AM
Certificate
U-109-7948
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8066
Sewer Name
SAN MARINO OUTFALL TRUNK
City
SAN MARINO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
17
Purpose
Routine Assessment
Project
RFIR_WO_855315_TV16060_OCT2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
16 in.
Width
16 in.
Upstream MH
16 0336
Downstream MH
16 0335
Dir. of Survey
Downstream
Length Surveyed
198 ft.
Total Length
198 ft.
Structural Index
4
Structural Quick
4E00
Structural Rating
120
O&M Index
2
O&M Quick
2G00
O&M Rating
78
Overall Index
3
Overall Quick
Overall Rating
198
Pipe schematic from manhole 16 0336 to 16 0335
MH: 16 0336MH: 16 0335downstream0 ft. MGO - General Observation - CONNECTION AT MH, 9 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 16 03360 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start17.3 ft. FM - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES33.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"36.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"50.7 ft. FM - Fracture Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES54.8 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start103.4 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"106.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"175.7 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 4"178.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"194.5 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish194.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish198 ft. AMH - Downstream Manhole, Survey Ends - 16 0335198 ft. MGO - General Observation - CONNECTION AT MH, 9 O'CLOCK

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    17.3 ft. - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES

    50.7 ft. - Fracture Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    54.8 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (18)

DistanceCodeObservation
0MGOCONNECTION AT MH, 9 O'CLOCK
194.5FM
175.7TFC
178.7TFC
2DAGS
17.3FM
0AMH16 0336
103.4TFA
36.5TFC
106.4TFC
0MWM
54.8FM
50.7FM
198AMH16 0335
194.5DAGS
0MWL
33.9TF
198MGOCONNECTION AT MH, 9 O'CLOCK

Properties (7)

additional_info
630138111820061
custom_field_three
MULTIPLE FRACTURE
custom_field_two
3
customer
1
datetime
2020-11-18T07:53:27-08:00
documentation
PRO PIPE
is_lateral_inspection
false