Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 18, 2020, 07:26 PM
  • 16 0312_16 0311 _11182020_114206.mp4

Date
11/18/2020
W/O
855315
Weather
Dry
Operator/Surveyor
N.Zahreddine
Sewer ID
Z00665
PipeID
P13363
Time
11:26 AM
Certificate
U-109-7948
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8066
Sewer Name
SAN MARINO OUTFALL TRUNK
City
SAN MARINO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_855315_TV16060_OCT2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
16 0312
Downstream MH
16 0311
Dir. of Survey
Downstream
Length Surveyed
172.8 ft.
Total Length
172.8 ft.
Structural Index
4
Structural Quick
4A00
Structural Rating
40
O&M Index
2
O&M Quick
4131
O&M Rating
73
Overall Index
3
Overall Quick
Overall Rating
113
Pipe schematic from manhole 16 0312 to 16 0311
MH: 16 0312MH: 16 0311downstream0 ft. MGO - General Observation - CONNECTION AT MH, 9 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 16 03120 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 30 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start3.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"4.1 ft. FM - Fracture Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES10 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"47.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"91.6 ft. RTB - Roots Tap Barrell, from 02 to 05 o'clock, 5 %, within 8 inches of joint: NO - ROOTS IN TRUNK91.6 ft. RBC - Roots Ball Connection, at 02 o'clock, 100 %91.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4" - ROOTS99.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"127.3 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES128.4 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start145.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"148 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"169.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish169.3 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish172.8 ft. AMH - Downstream Manhole, Survey Ends - 16 0311

Observation photos (6)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES

    4.1 ft. - Fracture Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES

  • Roots Ball Connection, at 02 o'clock, 100 %

    91.6 ft. - Roots Ball Connection, at 02 o'clock, 100 %

  • Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4" - ROOTS

    91.6 ft. - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4" - ROOTS

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    127.3 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    128.4 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (20)

DistanceCodeObservation
127.3FM
3.7TFC
91.6RTBROOTS IN TRUNK
2DAGS
169.3DAGS
0MGOCONNECTION AT MH, 9 O'CLOCK
0AMH16 0312
0MWM
0MWL
91.6RBC
47.8TFC
169.3FM
148TFC
145.7TF
128.4FM
99.8TF
10TF
172.8AMH16 0311
91.6TFROOTS
4.1FM

Properties (7)

additional_info
630138111820061
custom_field_three
MULTIPLE FRACTURE
custom_field_two
3
customer
1
datetime
2020-11-18T11:26:48-08:00
documentation
PRO PIPE
is_lateral_inspection
false