Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 16, 2020, 09:10 AM
  • 16 0572_16 0571_11162020_012746.mp4

Date
11/16/2020
W/O
855312
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00659
PipeID
P13623
Time
1:10 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8210
Sewer Name
LAMANDA PARK TRUNK
City
PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
11
Purpose
Routine Assessment
Project
WO_855312_TV16077_OCT2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
22 in.
Width
22 in.
Upstream MH
16 0572
Downstream MH
16 0571
Dir. of Survey
Downstream
Length Surveyed
253.8 ft.
Total Length
253.8 ft.
Structural Index
4
Structural Quick
5I3I
Structural Rating
395
O&M Index
4
O&M Quick
4H32
O&M Rating
197
Overall Index
4
Overall Quick
Overall Rating
592
Pipe schematic from manhole 16 0572 to 16 0571
MH: 16 0572MH: 16 0571downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 16 05722 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. RFB - Roots Fine Barrell, from 08 to 04 o'clock7.1 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start17.9 ft. RMB - Roots Medium Barrell, from 08 to 04 o'clock, 5 %, within 8 inches of joint: YES, Start36.7 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 8"87.7 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 8"112 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: YES, 8"130.3 ft. RMC - Roots Medium Connection, at 11 o'clock, 10 %, within 8 inches of joint: YES131.2 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 8"159 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 8"178.6 ft. RMC - Roots Medium Connection, at 11 o'clock, 15 %, within 8 inches of joint: YES179.1 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"210.8 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"230.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"230.3 ft. RFL - Roots Fine Lateral, from 09 to 03 o'clock251.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish251.9 ft. RMB - Roots Medium Barrell, from 08 to 04 o'clock, 5 %, within 8 inches of joint: YES, Finish251.9 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish253.8 ft. AMH - Downstream Manhole, Survey Ends - 16 0571

Observation photos (7)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Barrell, from 08 to 04 o'clock

    2 ft. - Roots Fine Barrell, from 08 to 04 o'clock

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    7.1 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Roots Medium Barrell, from 08 to 04 o'clock, 5 %, within 8 inches of joint: YES, Start

    17.9 ft. - Roots Medium Barrell, from 08 to 04 o'clock, 5 %, within 8 inches of joint: YES, Start

  • Roots Medium Connection, at 11 o'clock, 10 %, within 8 inches of joint: YES

    130.3 ft. - Roots Medium Connection, at 11 o'clock, 10 %, within 8 inches of joint: YES

  • Roots Medium Connection, at 11 o'clock, 15 %, within 8 inches of joint: YES

    178.6 ft. - Roots Medium Connection, at 11 o'clock, 15 %, within 8 inches of joint: YES

  • Roots Fine Lateral, from 09 to 03 o'clock

    230.3 ft. - Roots Fine Lateral, from 09 to 03 o'clock

Observations (22)

DistanceCodeObservation
36.7TFC
130.3RMC
0MWL
0MWM
131.2TFC
251.9SAP
87.7TFC
2SAP
159TFC
179.1TFC
210.8TFA
2RFB
112TFA
251.9RMB
251.9SRV
230.3TFA
230.3RFL
0AMH16 0572
178.6RMC
253.8AMH16 0571
7.1SRV
17.9RMB

Properties (6)

custom_field_three
REINFORCEMENT VISIBLE
custom_field_two
2
customer
1
datetime
2020-11-16T01:10:02-08:00
documentation
PRO PIPE
is_lateral_inspection
false