Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 16, 2020, 09:28 AM
  • 16 0571_16 0570_11162020_014251.mp4

Date
11/16/2020
W/O
855312
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00659
PipeID
P13622
Time
1:28 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8210
Sewer Name
LAMANDA PARK TRUNK
City
PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
11
Purpose
Routine Assessment
Project
WO_855312_TV16077_OCT2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
22 in.
Width
22 in.
Upstream MH
16 0571
Downstream MH
16 0570
Dir. of Survey
Downstream
Length Surveyed
249.5 ft.
Total Length
249.5 ft.
Structural Index
3
Structural Quick
3I00
Structural Rating
147
O&M Index
4
O&M Quick
4533
O&M Rating
29
Overall Index
3
Overall Quick
Overall Rating
176
Pipe schematic from manhole 16 0571 to 16 0570
MH: 16 0571MH: 16 0570downstream0 ft. AMH - Upstream Manhole, Survey Begins - 16 05710 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area2.8 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.8 ft. MGO - General Observation - MAG COAT8.2 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 8"31 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6"58.7 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6"58.7 ft. RBL - Roots Ball Lateral, from 08 to 08 o'clock, 75 %86.3 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"91 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"106.4 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"106.4 ft. RML - Roots Medium Lateral, from 08 to 04 o'clock, 10 %, within 8 inches of joint: YES123.6 ft. RMB - Roots Medium Barrell, from 08 to 04 o'clock, 5 %, within 8 inches of joint: YES, Start125.9 ft. RML - Roots Medium Lateral, from 08 to 04 o'clock, 25 %, within 8 inches of joint: YES125.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"143.7 ft. RMB - Roots Medium Barrell, from 08 to 04 o'clock, 5 %, within 8 inches of joint: YES, Finish157.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"157.6 ft. RML - Roots Medium Lateral, from 08 to 04 o'clock, 20 %, within 8 inches of joint: YES177.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"212.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"248.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish249.2 ft. MGO - General Observation - CONNECTION AT MH, 9 O'CLOCK249.5 ft. AMH - Downstream Manhole, Survey Ends - 16 0570

Observation photos (7)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.8 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - MAG COAT

    2.8 ft. - General Observation - MAG COAT

  • Roots Ball Lateral, from 08 to 08 o'clock, 75 %

    58.7 ft. - Roots Ball Lateral, from 08 to 08 o'clock, 75 %

  • Roots Medium Lateral, from 08 to 04 o'clock, 10 %, within 8 inches of joint: YES

    106.4 ft. - Roots Medium Lateral, from 08 to 04 o'clock, 10 %, within 8 inches of joint: YES

  • Roots Medium Barrell, from 08 to 04 o'clock, 5 %, within 8 inches of joint: YES, Start

    123.6 ft. - Roots Medium Barrell, from 08 to 04 o'clock, 5 %, within 8 inches of joint: YES, Start

  • Roots Medium Lateral, from 08 to 04 o'clock, 25 %, within 8 inches of joint: YES

    125.9 ft. - Roots Medium Lateral, from 08 to 04 o'clock, 25 %, within 8 inches of joint: YES

  • Roots Medium Lateral, from 08 to 04 o'clock, 20 %, within 8 inches of joint: YES

    157.6 ft. - Roots Medium Lateral, from 08 to 04 o'clock, 20 %, within 8 inches of joint: YES

Observations (24)

DistanceCodeObservation
0AMH16 0571
125.9RML
157.6RML
106.4TFC
106.4RML
249.5AMH16 0570
91TFA
123.6RMB
177.3TFC
0MWM
31TF
2.8SAP
58.7TF
0MWL
143.7RMB
58.7RBL
2.8MGOMAG COAT
125.9TFC
8.2TFC
157.5TFC
248.6SAP
249.2MGOCONNECTION AT MH, 9 O'CLOCK
212.7TFC
86.3TFC

Properties (6)

custom_field_three
AGGREGATE PROJECTING
custom_field_two
3
customer
1
datetime
2020-11-16T01:28:49-08:00
documentation
PRO PIPE
is_lateral_inspection
false