Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 10, 2017, 05:31 PM
  • 30 0269_30 0268_3102017_131444.mp4

  • 30 0269_30 0268_3102017_132729.mp4

Date
03/10/2017
W/O
0619108
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00876
PipeID
P17965
Time
9:31 AM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7357/7358
Sewer Name
30 PLAZA TRUNK
City
PALOS VERDES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 30
Page No.
09
Purpose
Routine Assessment
Project
20170310DF_PLAZA_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Upstream MH
30 0269
Downstream MH
30 0268
Dir. of Survey
Downstream
Length Surveyed
241 ft.
Total Length
241 ft.
Structural Index
3
Structural Quick
5341
Structural Rating
37
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
37
Pipe schematic from manhole 30 0269 to 30 0268
MH: 30 0269MH: 30 0268downstream0 ft. AMH - Upstream Manhole, Survey Begins - 1:12 PM0 ft. MWL - Water Level, 15 %of cross sectional area0.1 ft. MGO - General Observation - Conn. @ Mh, 5 O' Clock. Active0.1 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start27.3 ft. CC - Crack Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES33.4 ft. B - Broken, from 01 to 05 o'clock, within 8 inches of joint: YES33.4 ft. MGP - General Photograph - BROKEN34.1 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 4"37.9 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES37.9 ft. B - Broken, from 07 to 09 o'clock, within 8 inches of joint: YES47.9 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES57.8 ft. MGP - General Photograph - BROKEN57.8 ft. B - Broken, from 03 to 08 o'clock, within 8 inches of joint: YES67.7 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES77.6 ft. B - Broken, from 04 to 05 o'clock, within 8 inches of joint: YES77.6 ft. CM - Crack Multiple, from 03 to 05 o'clock, within 8 inches of joint: YES92.5 ft. CC - Crack Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES127 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES162.8 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 4" - 20% ROOTS213.1 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES240.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish241 ft. AMH - Downstream Manhole, Survey Ends - 2:07 PM

Observation photos (14)

  • Crack Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES

    27.3 ft. - Crack Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES

  • Broken, from 01 to 05 o'clock, within 8 inches of joint: YES

    33.4 ft. - Broken, from 01 to 05 o'clock, within 8 inches of joint: YES

  • General Photograph - BROKEN

    33.4 ft. - General Photograph - BROKEN

  • Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES

    37.9 ft. - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES

  • Broken, from 07 to 09 o'clock, within 8 inches of joint: YES

    37.9 ft. - Broken, from 07 to 09 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    47.9 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • General Photograph - BROKEN

    57.8 ft. - General Photograph - BROKEN

  • Broken, from 03 to 08 o'clock, within 8 inches of joint: YES

    57.8 ft. - Broken, from 03 to 08 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    67.7 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Broken, from 04 to 05 o'clock, within 8 inches of joint: YES

    77.6 ft. - Broken, from 04 to 05 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 03 to 05 o'clock, within 8 inches of joint: YES

    77.6 ft. - Crack Multiple, from 03 to 05 o'clock, within 8 inches of joint: YES

  • Crack Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES

    92.5 ft. - Crack Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    127 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    213.1 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

Observations (23)

DistanceCodeObservation
241AMH2:07 PM
0.1MGOConn. @ Mh, 5 O' Clock. Active
47.9CL
77.6B
213.1CL
57.8MGPBROKEN
2SSS
0AMH1:12 PM
27.3CC
77.6CM
162.8TF20% ROOTS
92.5CC
37.9FL
127CL
34.1TFC
240.3SSS
57.8B
67.7CL
0.1MWM
33.4B
37.9B
0MWL
33.4MGPBROKEN

Properties (4)

customer
LACSD
datetime
2017-03-10T09:31:47-08:00
documentation
FRANKLIN, BRAR
is_lateral_inspection
false