Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 19, 2020, 11:17 AM
  • 02 0005_02 0132_11192020_032303.mp4

Date
11/19/2020
W/O
855305
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00234
PipeID
P03030
Time
3:17 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8306
Sewer Name
ARTESIA EXTENSION TRUNK
City
BELLFLOWER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
38
Purpose
Routine Assessment
Project
RFIR_WO_855305_TV02263_OCT2020
Sewer Type
Siphon
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Width
15 in.
Upstream MH
02 0005
Downstream MH
02 0132
Dir. of Survey
Downstream
Length Surveyed
6.2 ft.
Total Length
6.2 ft.
Structural Index
4
Structural Quick
5232
Structural Rating
16
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
16
Pipe schematic from manhole 02 0005 to 02 0132
MH: 02 0005MH: 02 0132downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 0005 NORTH0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - AIR LINE VISIBLE @ 12 O'CLOCK ABOVE NORTH BARREL2.1 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Start2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start6.2 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Finish6.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish6.2 ft. MSA - Survey Abandoned - VIEW OF D/S SIPHON FROM U/S MH

Observation photos (3)

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Survey Abandoned - VIEW OF D/S SIPHON FROM U/S MH

    6.2 ft. - Survey Abandoned - VIEW OF D/S SIPHON FROM U/S MH

Observations (9)

DistanceCodeObservation
0AMH02 0005 NORTH
0MWL
2.1SRV
6.2SRV
0MWM
6.2SAP
6.2MSAVIEW OF D/S SIPHON FROM U/S MH
0MGOAIR LINE VISIBLE @ 12 O'CLOCK ABOVE NORTH BARREL
2.1SAP

Properties (7)

additional_info
630075111820204
custom_field_three
AGGREGATE PROJECTING/REINFORCEMENT VISIBLE
custom_field_two
2
customer
1
datetime
2020-11-19T03:17:42-08:00
documentation
PROPIPE
is_lateral_inspection
false