Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 18, 2020, 08:41 AM
  • 08 0463_08 0477 _11182020_020226.mp4

Date
11/18/2020
W/O
855102
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00025
PipeID
P00535
Time
12:41 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8302
Sewer Name
216TH STREET RELOCATION TRUNK
City
CARSON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_855102_TV08140_OCT2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Width
12 in.
Upstream MH
08 0463
Downstream MH
08 0477
Dir. of Survey
Downstream
Length Surveyed
791.3 ft.
Total Length
791.3 ft.
Structural Index
3
Structural Quick
5_3_
Structural Rating
1590
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
1594
Pipe schematic from manhole 08 0463 to 08 0477
MH: 08 0463MH: 08 0477downstream0 ft. MWL - Water Level, 45 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWM - Water Mark, 60 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 04632.1 ft. MGO - General Observation - MAG COAT2.1 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start102 ft. SRC - Surface Reinforcement Corroded, from 12 to 03 o'clock, within 8 inches of joint: YES, Start - BROKEN REBAR380 ft. SRC - Surface Reinforcement Corroded, from 12 to 03 o'clock, within 8 inches of joint: YES, Finish791.3 ft. AMH - Downstream Manhole, Survey Ends - 08 0477791.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish791.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish791.3 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish

Observation photos (3)

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
791.3AMH08 0477
2.1MGOMAG COAT
102SRCBROKEN REBAR
380SRC
2.1SRV
0MWL
791.3SAP
0MGOCONNECTION AT MH 9 O'CLOCK
0MWM
2.1SSS
791.3SSS
2.1SAP
0AMH08 0463
791.3SRV

Properties (7)

additional_info
630075111720202
custom_field_three
REINFORCEMENT VISIBLE/AGGREGATE PROJECTING
custom_field_two
2
customer
1
datetime
2020-11-18T00:41:57-08:00
documentation
PROPIPE
is_lateral_inspection
false