Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 13, 2020, 03:54 PM
  • 08 0596_D 0008 _11132020_083457.mp4

Date
11/13/2020
W/O
855308
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00025
PipeID
P00530
Time
7:54 AM
Certificate
U-109-7948
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8063
Sewer Name
216TH STREET RELOCATION TRUNK
City
CARSON
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_855308_TV08101_OCT2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Width
30 in.
Upstream MH
08 0596
Downstream MH
D 0008
Dir. of Survey
Downstream
Length Surveyed
699.1 ft.
Total Length
699.1 ft.
Structural Index
4
Structural Quick
5Z3Z
Structural Rating
1096
O&M Index
3
O&M Quick
4121
O&M Rating
6
Overall Index
4
Overall Quick
Overall Rating
1102
Pipe schematic from manhole 08 0596 to D 0008
MH: 08 0596MH: D 0008downstream0 ft. AMH - Upstream Manhole, Survey Begins - 08 05960 ft. MWM - Water Mark, 55 %of cross sectional area0 ft. MWL - Water Level, 40 %of cross sectional area2 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. MGO - General Observation - M.H.O COATING START2 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start444.2 ft. OBZ - Obstacles Other, 5 %of cross sectional area, at 12 o'clock - reinforcement hanging689.1 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish689.1 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish691.4 ft. MGO - General Observation - M.H.O.COATIN END699 ft. MGO - General Observation - CONNECTION AT MH, 3 O'CLOCK699.1 ft. AMH - Downstream Manhole, Survey Ends - D 0008

Observation photos (3)

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Obstacles Other, 5 %of cross sectional area, at 12 o'clock - reinforcement hanging

    444.2 ft. - Obstacles Other, 5 %of cross sectional area, at 12 o'clock - reinforcement hanging

Observations (12)

DistanceCodeObservation
2SAV
0AMH08 0596
689.1SRV
691.4MGOM.H.O.COATIN END
2MGOM.H.O COATING START
689.1SAV
699MGOCONNECTION AT MH, 3 O'CLOCK
699.1AMHD 0008
444.2OBZreinforcement hanging
2SRV
0MWM
0MWL

Properties (7)

additional_info
630138111320201
custom_field_three
surface reinf. visible and corroded
custom_field_two
2
customer
1
datetime
2020-11-13T07:54:11-08:00
documentation
PRO PIPE
is_lateral_inspection
false