Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 12, 2020, 09:34 AM
  • 15 0613A_15 0613 _11122020_014111.mp4

Date
11/12/2020
W/O
855316
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00601
PipeID
P12550
Time
1:34 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8190
Sewer Name
DOUBLE AVENUE TRUNK
City
TEMPLE CITY
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
11
Purpose
Routine Assessment
Project
RFIR_WO_855316_TV15205_OCT2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
15 0613A
Downstream MH
15 0613
Dir. of Survey
Downstream
Length Surveyed
134.5 ft.
Total Length
134.5 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
8
Pipe schematic from manhole 15 0613A to 15 0613
MH: 15 0613AMH: 15 0613downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 0613A0 ft. MGO - General Observation - CONNECTION AT MH 3 AND 9 OCLOCK2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start29.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start64.1 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"67.1 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 6"133.7 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish133.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish133.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish134.5 ft. MGO - General Observation - ROACHES IN MH134.5 ft. AMH - Downstream Manhole, Survey Ends - 15 0613

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    29.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - ROACHES IN MH

    134.5 ft. - General Observation - ROACHES IN MH

Observations (14)

DistanceCodeObservation
0MWM
29.1CM
0MWL
64.1TFA
2DAGS
134.5MGOROACHES IN MH
67.1TF
0AMH15 0613A
2.1SAP
0MGOCONNECTION AT MH 3 AND 9 OCLOCK
133.7SAP
134.5AMH15 0613
133.7DAGS
133.7CM

Properties (7)

additional_info
630069111220001
custom_field_three
PROJECTING AGGREGATE/MULTIPLE CRACKS
custom_field_two
2
customer
1
datetime
2020-11-12T01:34:20-08:00
documentation
PRO PIPE
is_lateral_inspection
false