Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 12, 2020, 10:05 AM
  • 15 0612_15 0611_11122020_021515.mp4

Date
11/12/2020
W/O
855316
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00601
PipeID
P12547
Time
2:05 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8190
Sewer Name
DOUBLE AVENUE TRUNK
City
TEMPLE CITY
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
11
Purpose
Routine Assessment
Project
RFIR_WO_855316_TV15205_OCT2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
15 0612
Downstream MH
15 0611
Dir. of Survey
Downstream
Length Surveyed
137.4 ft.
Total Length
137.4 ft.
Structural Index
3
Structural Quick
4132
Structural Rating
10
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
12
Pipe schematic from manhole 15 0612 to 15 0611
MH: 15 0612MH: 15 0611downstream0 ft. AMH - Upstream Manhole, Survey Begins - 15 0612, ABANDONED MH.0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start7 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES15.2 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start20.9 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"23.5 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"81.2 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"95.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"135.3 ft. MGO - General Observation - ROACHES IN MH135.3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish135.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish135.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish137.4 ft. AMH - Downstream Manhole, Survey Ends - 15 0611137.4 ft. MGO - General Observation - CONNECTION AT MH 3 OCLOCK

Observation photos (6)

  • Upstream Manhole, Survey Begins - 15 0612, ABANDONED MH.

    0 ft. - Upstream Manhole, Survey Begins - 15 0612, ABANDONED MH.

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    7 ft. - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    15.2 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - ROACHES IN MH

    135.3 ft. - General Observation - ROACHES IN MH

Observations (17)

DistanceCodeObservation
0AMH15 0612, ABANDONED MH.
81.2TFA
95.4TFC
2DAGS
20.9TBA
0MWL
2SAP
7FL
135.3MGOROACHES IN MH
0MWM
135.3FM
135.3DAGS
15.2FM
137.4AMH15 0611
135.3SAP
23.5TFA
137.4MGOCONNECTION AT MH 3 OCLOCK

Properties (7)

additional_info
630069111220001
custom_field_three
PROJECTING AGGREGATE/FRACTURES
custom_field_two
2
customer
1
datetime
2020-11-12T02:05:57-08:00
documentation
PRO PIPE
is_lateral_inspection
false