Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 12, 2020, 10:41 AM
  • 15 0610_15 0609A _11122020_025258.mp4

Date
11/12/2020
W/O
855316
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00601
PipeID
P12544
Time
2:41 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8190
Sewer Name
DOUBLE AVENUE TRUNK
City
TEMPLE CITY
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
11
Purpose
Routine Assessment
Project
RFIR_WO_855316_TV15205_OCT2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
15 0609A
Downstream MH
15 0610
Dir. of Survey
Upstream
Length Surveyed
230.1 ft.
Total Length
230.1 ft.
Structural Index
3
Structural Quick
4H3H
Structural Rating
307
O&M Index
2
O&M Quick
2H00
O&M Rating
90
Overall Index
3
Overall Quick
Overall Rating
397
Pipe schematic from manhole 15 0609A to 15 0610
MH: 15 0609AMH: 15 0610upstream0 ft. AMH - Upstream Manhole, Survey Ends - 15 06100.1 ft. MGO - General Observation - CONNECTIONS AT 3 AND 9 O'CLOCK1.7 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish1.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish1.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish66.2 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"95 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"152.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"186.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"215.4 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start228.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start228.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start230.1 ft. MGO - General Observation - CONNECTION AT MH 3 OCLOCK230.1 ft. MWL - Water Level, 5 %of cross sectional area230.1 ft. AMH - Downstream Manhole, Survey Begins - 15 0609A230.1 ft. MWM - Water Mark, 15 %of cross sectional area

Observation photos (3)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    14.7 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (16)

DistanceCodeObservation
43.9TFC
228.4SAV
2SAV
0MGOCONNECTION AT MH 3 OCLOCK
0MWL
0AMH15 0609A
0MWM
163.9TFA
230.1AMH15 0610
14.7FM
228.4FM
77.2TFA
2DAGS
228.4DAGS
230MGOCONNECTIONS AT 3 AND 9 O'CLOCK
135.1TFC

Properties (7)

additional_info
630069111220001
custom_field_three
PROJECTING AGGREGATE/FRACTURES
custom_field_two
2
customer
1
datetime
2020-11-12T02:41:26-08:00
documentation
PRO PIPE
is_lateral_inspection
false