Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 29, 2020, 09:25 AM
  • 14 0117_14 0116A_10292020_024240.mp4

Date
10/29/2020
W/O
850052
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00571
PipeID
P25683
Time
2:25 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8176
Sewer Name
DISTRICT #14 OUTFALL TRUNK
City
LANCASTER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
05
Purpose
Routine Assessment
Project
RFIR_WO_850052_TV14075_SEP2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
14 0117
Downstream MH
14 0116A
Dir. of Survey
Downstream
Length Surveyed
404.5 ft.
Total Length
404.5 ft.
Structural Index
3
Structural Quick
493M
Structural Rating
246
O&M Index
2
O&M Quick
2O00
O&M Rating
160
Overall Index
3
Overall Quick
Overall Rating
406
Pipe schematic from manhole 14 0117 to 14 0116A
MH: 14 0117MH: 14 0116Adownstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 14 01172 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start6.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start9.8 ft. TBA - Tap Break-In Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"95.4 ft. TBA - Tap Break-In Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"99.4 ft. TBA - Tap Break-In Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"148 ft. TBA - Tap Break-In Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"210.1 ft. TBA - Tap Break-In Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"254.1 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"356 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start356 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish359.2 ft. TBA - Tap Break-In Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"402.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish402.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish404.5 ft. AMH - Downstream Manhole, Survey Ends - 14 0116A404.5 ft. MGO - General Observation - ACTIVE CONNECTION AT MH, 9 O'CLOCK

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6.4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    356 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - ACTIVE CONNECTION AT MH, 9 O'CLOCK

    404.5 ft. - General Observation - ACTIVE CONNECTION AT MH, 9 O'CLOCK

Observations (18)

DistanceCodeObservation
0MWL
356FM
9.8TBA
402.6DAGS
2DAGS
95.4TBA
404.5AMH14 0116A
359.2TBA
402.6FM
254.1TBA
148TBA
6.4CM
210.1TBA
404.5MGOACTIVE CONNECTION AT MH, 9 O'CLOCK
356CM
0MWM
99.4TBA
0AMH14 0117

Properties (7)

additional_info
6301028200138P2
custom_field_three
MULTIPLE FRACTURES/MULTIPLE CRACKS
custom_field_two
2
customer
1
datetime
2020-10-29T02:25:02-07:00
documentation
PRO PIPE
is_lateral_inspection
false