Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 29, 2020, 08:56 AM
  • 14 0121_14 0120_10292020_021144.mp4

Date
10/29/2020
W/O
850052
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00571
PipeID
P18151
Time
1:56 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8176
Sewer Name
DISTRICT #14 OUTFALL TRUNK
City
LANCASTER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_850052_TV14075_SEP2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
14 0121
Downstream MH
14 0120
Dir. of Survey
Downstream
Length Surveyed
290.1 ft.
Total Length
290.1 ft.
Structural Index
3
Structural Quick
413J
Structural Rating
175
O&M Index
2
O&M Quick
2J00
O&M Rating
114
Overall Index
3
Overall Quick
Overall Rating
289
Pipe schematic from manhole 14 0121 to 14 0120
MH: 14 0121MH: 14 0120downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 14 01210 ft. MGO - General Observation - ACTIVE CONNECTION AT MH, 9 O'CLOCK2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start4.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start6.7 ft. TBA - Tap Break-In Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"59.6 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"73.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES116.4 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"127.9 ft. TBA - Tap Break-In Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"174.1 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"201.9 ft. TBA - Tap Break-In Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"226.4 ft. TBA - Tap Break-In Active, at 03 o'clock, -, within 8 inches of joint: YES, 6"266.7 ft. TBA - Tap Break-In Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"287.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish287.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish290.1 ft. AMH - Downstream Manhole, Survey Ends - 14 0120

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.9 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    73.6 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (18)

DistanceCodeObservation
287.9CM
201.9TBA
0MWM
2DAGS
0MWL
174.1TBA
290.1AMH14 0120
127.9TBA
116.4TBA
73.6FM
4.9CM
266.7TBA
6.7TBA
226.4TBA
0AMH14 0121
287.9DAGS
0MGOACTIVE CONNECTION AT MH, 9 O'CLOCK
59.6TBA

Properties (7)

additional_info
6301028200138P2
custom_field_three
MULTIPLE CRACKS/MULTIPLE FRACTURES
custom_field_two
2
customer
1
datetime
2020-10-29T01:56:40-07:00
documentation
PRO PIPE
is_lateral_inspection
false