Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 29, 2020, 09:57 AM
  • 14 0114_14 0740 _10292020_031035.mp4

Date
10/29/2020
W/O
850052
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00571
PipeID
P18144
Time
2:57 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8176
Sewer Name
DISTRICT #14 OUTFALL TRUNK
City
LANCASTER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
05
Purpose
Routine Assessment
Project
RFIR_WO_850052_TV14075_SEP2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
14 0114
Downstream MH
14 0740
Dir. of Survey
Downstream
Length Surveyed
276.1 ft.
Total Length
276.1 ft.
Structural Index
4
Structural Quick
4E3D
Structural Rating
193
O&M Index
2
O&M Quick
412J
O&M Rating
114
Overall Index
3
Overall Quick
Overall Rating
307
Pipe schematic from manhole 14 0114 to 14 0740
MH: 14 0114MH: 14 0740downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 14 01142 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start9.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start74 ft. RPZ - Repair Other, within 8 inches of joint: YES90.3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES126.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish126.2 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start274.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish274.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish276.1 ft. AMH - Downstream Manhole, Survey Ends - 14 0740, RUN LIST STATES MH AT 318'.

Observation photos (5)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    9.9 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Repair Other, within 8 inches of joint: YES

    74 ft. - Repair Other, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    90.3 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    126.2 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
90.3FM
274.7DAGS
274.7FM
9.9CM
0MWL
276.1AMH14 0740, RUN LIST STATES MH AT 318'.
74RPZ
2DAGS
0MWM
126.2CM
0AMH14 0114
126.2FM

Properties (7)

additional_info
6301028200138P2
custom_field_three
MULTIPLE CRACKS/MULTIPLE FRACTURES
custom_field_two
2
customer
1
datetime
2020-10-29T02:57:26-07:00
documentation
PRO PIPE
is_lateral_inspection
false