Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 29, 2020, 06:46 AM
  • 29 0438_29 0432_10282020_225458.mp4

Date
10/28/2020
W/O
855310
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00989
PipeID
P24475
Time
11:46 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8139
Sewer Name
LEWIS AVENUE SEWER
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
01
Purpose
Routine Assessment
Project
RFIR_WO_855310_TV29059_OCT2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0432
Downstream MH
29 0438
Dir. of Survey
Upstream
Length Surveyed
134.9 ft.
Total Length
134.9 ft.
Structural Index
4
Structural Quick
5131
Structural Rating
8
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
8
Pipe schematic from manhole 29 0432 to 29 0438
MH: 29 0432MH: 29 0438upstream0 ft. ACOM - Cleanout Mainline, Survey Ends - 29 04380 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish2.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"5.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"33.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"57.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"124.5 ft. B - Broken, from 01 to 03 o'clock, within 8 inches of joint: YES132.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start134.9 ft. AMH - Downstream Manhole, Survey Begins - 29 0432134.9 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK134.9 ft. MWM - Water Mark, 5 %of cross sectional area134.9 ft. MWL - Water Level, 5 %of cross sectional area

Observation photos (2)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Broken, from 01 to 03 o'clock, within 8 inches of joint: YES

    10.4 ft. - Broken, from 01 to 03 o'clock, within 8 inches of joint: YES

Observations (12)

DistanceCodeObservation
77TFC
10.4B
101TF
0AMH29 0432
129.5TF
2.1CM
0MGOCONNECTION AT MH 9 O'CLOCK
132TF
134.9ACOM29 0438
134.9CM
0MWM
0MWL

Properties (7)

additional_info
SC411969
custom_field_three
MULTIPLE CRACKS
custom_field_two
2
customer
1
datetime
2020-10-28T23:46:46-07:00
documentation
propipe
is_lateral_inspection
false