G 0320_G 0319_11192020_014643.mp4
2 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG AREAS OF MISSING TILES
8 ft. - General Observation - MISSING TILES 30% START
37.3 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR
38.9 ft. - Surface Reinforcement Corroded, from 12 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR CORRODED & MISSING
43.6 ft. - General Observation - 100% MISSING TILES
55.9 ft. - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM
60.7 ft. - Surface Reinforcement Corroded, from 11 to 02 o'clock, within 8 inches of joint: NO - CIRCUM
118.9 ft. - Surface Reinforcement Corroded, from 12 to 03 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR
144.8 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM
| Distance | Code | Observation |
|---|---|---|
| 65.6 | MGO | 30% MISSING TILES |
| 170.9 | AMH | 2:15AM |
| 118.9 | SRC | LONG CIRCUM REBAR |
| 141 | SRV | CIRCUM |
| 2 | MGO | MISSING TILES 10% START |
| 60.7 | SRC | CIRCUM |
| 144.8 | SRV | CIRCUM |
| 0 | MWL | — |
| 55.9 | SRC | CIRCUM |
| 104.6 | DSZ | FALLEN TILES UNDER FLOW |
| 0 | MWM | — |
| 0 | AMH | 1:45AM |
| 38.9 | MGO | MISSING TILES 50% IN SECTIONS |
| 2 | SAM | SEVERE AGG AREAS OF MISSING TILES |
| 37.3 | SRC | CIRCUM REBAR |
| 38.9 | SRC | CIRCUM REBAR CORRODED & MISSING |
| 8 | MGO | MISSING TILES 30% START |
| 43.6 | MGO | 100% MISSING TILES |
| 170.2 | SAM | SEVERE AGG AREAS OF MISSING TILES |