Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 20, 2020, 08:58 AM
  • 02 1658_02 1657A_11202020_033033.mp4

Date
11/20/2020
W/O
0860090
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00289
PipeID
P18814
Time
12:58 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1634
Sewer Name
02 MONTEREY PARK EXTENSION TRUNK
City
LOS ANGELES
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
09
Purpose
Capital Improvement Program Assesment
Project
20201120MDM_MONTERY_PARK_EXTENSION_TRUNK
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
02 1658
Downstream MH
02 1657A
Dir. of Survey
Downstream
Length Surveyed
110.7 ft.
Total Length
110.7 ft.
Structural Index
3
Structural Quick
4221
Structural Rating
10
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
10
Pipe schematic from manhole 02 1658 to 02 1657A
MH: 02 1658MH: 02 1657Adownstream0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 3:30AM2 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - FLAKING CONCRETE84.9 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG84.9 ft. MGO - General Observation - 15" NRCP97 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open100.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open110 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - FLAKING CONCRETE110 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG110 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active110.7 ft. AMH - Downstream Manhole, Survey Ends - 3:45AM

Observation photos (4)

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - FLAKING CONCRETE

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - FLAKING CONCRETE

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

    84.9 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • General Observation - 15" NRCP

    84.9 ft. - General Observation - 15" NRCP

Observations (15)

DistanceCodeObservation
0MGOConn. @ Mh, 9 O' Clock. Active
110SSSFLAKING CONCRETE
0MGOConn. @ Mh, 3 O' Clock. Active
2SAMSEVERE AGG
110.7AMH3:45AM
110SAMSEVERE AGG
100.5TFCOpen
110MGOConn. @ Mh, 3 O' Clock. Active
84.9SAMSEVERE AGG
0MWL
84.9MGO15" NRCP
97TFCOpen
0MWM
2SSSFLAKING CONCRETE
0AMH3:30AM

Properties (6)

custom_field_three
SEVERE AGG MISSING
custom_field_two
2
customer
LACSD
datetime
2020-11-20T00:58:51-08:00
documentation
MARTIN,OLIVER 111,CASTILLO,RUVALCABA
is_lateral_inspection
false