Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 22, 2020, 08:07 PM
  • 3_1_1_22102020_131322.mp4

Date
10/22/2020
W/O
0853364
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00139
PipeID
P09816
Time
1:07 PM
Certificate
U-415-06024039
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0352
Sewer Name
JOINT OUTFALL C - UNIT 8A
City
LONG BEACH
Loc. details
Other
Location Code
Z
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
09
Purpose
Routine Assessment
Project
20201020DF_JOINT_OUTFALL_C_UNIT_8A
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
42 in.
Upstream MH
C 0353
Downstream MH
C 0352
Dir. of Survey
Downstream
Length Surveyed
789.3 ft.
Total Length
793.4 ft.
Structural Index
3
Structural Quick
5^3^
Structural Rating
1570
O&M Index
3
O&M Quick
4^2^
O&M Rating
942
Overall Index
3
Overall Quick
Overall Rating
2512
Pipe schematic from manhole C 0353 to C 0352
MH: C 0353MH: C 0352downstream0 ft. AMH - Upstream Manhole, Survey Begins - 1:09 PM0.1 ft. MWL - Water Level, 20 %of cross sectional area1 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. IR - Infiltration Runner, from 08 to 04 o'clock, within 8 inches of joint: YES, Start760 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 4", 4"789.3 ft. IR - Infiltration Runner, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish789.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish789.3 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish789.3 ft. AMH - Downstream Manhole, Survey Ends - 2:07 PM789.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish789.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (6)

  • Upstream Manhole, Survey Begins - 1:09 PM

    0 ft. - Upstream Manhole, Survey Begins - 1:09 PM

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Infiltration Runner, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Infiltration Runner, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (15)

DistanceCodeObservation
0AMH1:09 PM
760TFA
0.1MWL
2DAGS
2SSS
2SAP
1MWM
789.3IR
789.3DAGS
789.3SRC
2SRC
789.3AMH2:07 PM
789.3SAP
789.3SSS
2IR

Properties (7)

additional_info
The footage was adjusted according to previous inspections - Equipment Malfunction - Footage Counter not working during the inspection.
custom_field_three
AGGREGATE PROJECTING/INFILTRATION THROUGHOUT
custom_field_two
2
customer
1
datetime
2020-10-22T13:07:32-07:00
documentation
FRANKLIN, SHADLER, IGNACIO, RAMIREZ, BRAR
is_lateral_inspection
false