Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 10, 2020, 09:07 AM
  • 04 0054_04 0053_11102020_012713.mp4

Date
11/10/2020
W/O
855017
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00412
PipeID
P11783
Time
1:07 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8186
Sewer Name
LA CIENEGA BOULEVARD TRUNK
City
WEST HOLLYWOOD
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 04
Page No.
01
Purpose
Routine Assessment
Project
RFIR_WO_855017_TV04019_OCT2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
04 0054
Downstream MH
04 0053
Dir. of Survey
Downstream
Length Surveyed
294.8 ft.
Total Length
294.8 ft.
Structural Index
4
Structural Quick
5133
Structural Rating
14
O&M Index
3
O&M Quick
4121
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
20
Pipe schematic from manhole 04 0054 to 04 0053
MH: 04 0054MH: 04 0053downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 04 00542 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start18.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start61.4 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"61.4 ft. H - Hole, at 10 o'clock, within 8 inches of joint: NO64.2 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"92.8 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"106.2 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"118 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"132.8 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"141.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"144.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"164.6 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"186.9 ft. HSV - Hole Soil Visible, at 10 o'clock, within 8 inches of joint: NO186.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"194.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"219.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"242.3 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"245.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"262.2 ft. H - Hole, at 03 o'clock, within 8 inches of joint: YES264.3 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"265.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"269.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"289.4 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"292.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish292.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish294.8 ft. MGO - General Observation - ROACHES IN MH294.8 ft. AMH - Downstream Manhole, Survey Ends - 04 0053

Observation photos (6)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    18.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Hole, at 10 o'clock, within 8 inches of joint: NO

    61.4 ft. - Hole, at 10 o'clock, within 8 inches of joint: NO

  • Hole Soil Visible, at 10 o'clock, within 8 inches of joint: NO

    186.9 ft. - Hole Soil Visible, at 10 o'clock, within 8 inches of joint: NO

  • Hole, at 03 o'clock, within 8 inches of joint: YES

    262.2 ft. - Hole, at 03 o'clock, within 8 inches of joint: YES

  • General Observation - ROACHES IN MH

    294.8 ft. - General Observation - ROACHES IN MH

Observations (30)

DistanceCodeObservation
264.3TB
164.6TFA
186.9HSV
0MWL
64.2TFA
262.2H
292.8DAGS
292.8CM
61.4TFA
132.8TBA
294.8MGOROACHES IN MH
289.4TFA
186.9TFA
242.3TB
141.5TFA
0MWM
144.6TFA
265.9TFC
61.4H
92.8TFA
2DAGS
106.2TFA
0AMH04 0054
294.8AMH04 0053
18.3CM
219.2TFA
269.3TFA
118TFA
194.5TFA
245.9TFC

Properties (7)

additional_info
6301109200069P2
custom_field_three
CRACKS/HOLES
custom_field_two
2
customer
1
datetime
2020-11-10T01:07:15-08:00
documentation
PRO PIPE
is_lateral_inspection
false