Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 12, 2020, 12:07 PM
  • 15 0606_15 0605A_11122020_041654.mp4

Date
11/12/2020
W/O
854911
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00601
PipeID
P26432
Time
4:07 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8191
Sewer Name
DOUBLE AVENUE TRUNK
City
TEMPLE CITY
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
11
Purpose
Routine Assessment
Project
RFIR_WO_854911_TV15183_OCT2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
15 0606
Downstream MH
15 0605A
Dir. of Survey
Downstream
Length Surveyed
204.7 ft.
Total Length
204.7 ft.
Structural Index
2
Structural Quick
3G2G
Structural Rating
202
O&M Index
2
O&M Quick
2G00
O&M Rating
80
Overall Index
2
Overall Quick
Overall Rating
282
Pipe schematic from manhole 15 0606 to 15 0605A
MH: 15 0606MH: 15 0605Adownstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 06060 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - ROACHES IN MH0 ft. MGO - General Observation - CONN @ MH 9 OCLOCK/ACTIVE2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start34 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"52.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"134 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"140.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"202 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish202.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish202.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish202.5 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES204.7 ft. AMH - Downstream Manhole, Survey Ends - 15 0605A204.7 ft. MGO - General Observation - CONN @ MH 3 OCLOCK/ACTIVE

Observation photos (4)

  • General Observation - ROACHES IN MH

    0 ft. - General Observation - ROACHES IN MH

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.5 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    202.5 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

Observations (18)

DistanceCodeObservation
2DAGS
202.5SAP
202.5DAGS
0MWM
204.7AMH15 0605A
202SSS
204.7MGOCONN @ MH 3 OCLOCK/ACTIVE
0AMH15 0606
134TFC
202.5CL
0MWL
2SSS
2.5SAP
52.2TFA
0MGOROACHES IN MH
0MGOCONN @ MH 9 OCLOCK/ACTIVE
140.6TFC
34TFC

Properties (7)

additional_info
630069111220002
custom_field_three
PROJECTING AGGREGATE/CRACK
custom_field_two
3
customer
1
datetime
2020-11-12T04:07:44-08:00
documentation
PRO PIPE
is_lateral_inspection
false