Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 12, 2020, 11:53 AM
  • 15 0607A_15 0607_11122020_040058.mp4

Date
11/12/2020
W/O
854911
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00601
PipeID
P12540
Time
3:53 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8191
Sewer Name
DOUBLE AVENUE TRUNK
City
TEMPLE CITY
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
11
Purpose
Routine Assessment
Project
RFIR_WO_854911_TV15183_OCT2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
15 0607A
Downstream MH
15 0607
Dir. of Survey
Downstream
Length Surveyed
158.4 ft.
Total Length
158.4 ft.
Structural Index
3
Structural Quick
3E2E
Structural Rating
155
O&M Index
2
O&M Quick
2E00
O&M Rating
62
Overall Index
2
Overall Quick
Overall Rating
217
Pipe schematic from manhole 15 0607A to 15 0607
MH: 15 0607AMH: 15 0607downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MGO - General Observation - CONN @ MH 3 OCLOCK/ACTIVE0 ft. AMH - Upstream Manhole, Survey Begins - 15 0607A0 ft. MWM - Water Mark, 10 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start51.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"87.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"130.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN156 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish156.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish156.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish158.4 ft. MGO - General Observation - CONN @ MH 9 OCLOCK/OPEN158.4 ft. MGO - General Observation - ROACHES IN MH158.4 ft. AMH - Downstream Manhole, Survey Ends - 15 0607

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.5 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - ROACHES IN MH

    158.4 ft. - General Observation - ROACHES IN MH

Observations (16)

DistanceCodeObservation
158.4MGOCONN @ MH 9 OCLOCK/OPEN
87.3TFA
0MWL
0MGOCONN @ MH 3 OCLOCK/ACTIVE
130.4TFOPEN
158.4MGOROACHES IN MH
0AMH15 0607A
156SSS
156.1SAP
156.1DAGS
2.5SAP
2SSS
51.2TFA
0MWM
158.4AMH15 0607
2DAGS

Properties (7)

additional_info
630069111220002
custom_field_three
PROJECTING AGGREGATE
custom_field_two
3
customer
1
datetime
2020-11-12T03:53:33-08:00
documentation
PRO PIPE
is_lateral_inspection
false