Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 12, 2020, 12:17 PM
  • 15 0605A_15 0605_11122020_042218.mp4

Date
11/12/2020
W/O
854911
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00601
PipeID
P12538
Time
4:17 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8191
Sewer Name
DOUBLE AVENUE TRUNK
City
TEMPLE CITY
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
11
Purpose
Routine Assessment
Project
RFIR_WO_854911_TV15183_OCT2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
15 0605A
Downstream MH
15 0605
Dir. of Survey
Downstream
Length Surveyed
6.8 ft.
Total Length
6.8 ft.
Structural Index
2
Structural Quick
3122
Structural Rating
7
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
11
Pipe schematic from manhole 15 0605A to 15 0605
MH: 15 0605AMH: 15 0605downstream0 ft. MGO - General Observation - CONN @ MH 3 OCLOCK/ACTIVE0 ft. AMH - Upstream Manhole, Survey Begins - 15 0605A0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start4.6 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish6.8 ft. AMH - Downstream Manhole, Survey Ends - 15 06056.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish6.8 ft. MGO - General Observation - CONN @ MH 3 OCLOCK/ACTIVE6.8 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE6.8 ft. MGO - General Observation - ROACHES IN MH

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - ROACHES IN MH

    6.8 ft. - General Observation - ROACHES IN MH

Observations (13)

DistanceCodeObservation
6.8AMH15 0605
0MGOCONN @ MH 3 OCLOCK/ACTIVE
4.6SAP
6.8DAGS
6.8MGOCONN @ MH 3 OCLOCK/ACTIVE
6.8MGOCONN @ MH 9 O'CLOCK/ACTIVE
2DAGS
0AMH15 0605A
0MWM
6.8MGOROACHES IN MH
2SSS
5SSS
0MWL

Properties (7)

additional_info
630069111220002
custom_field_three
PROJECTING AGGREGATE
custom_field_two
3
customer
1
datetime
2020-11-12T04:17:26-08:00
documentation
PRO PIPE
is_lateral_inspection
false