Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 29, 2020, 10:20 AM
  • 08 0161_08 0160_09292020_032417.mp4

Date
09/29/2020
W/O
850134
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00009
PipeID
P00218
Time
3:20 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8101
Sewer Name
GRACE STREET TRUNK, SECTION 1
City
CARSON
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Routine Assessment
Project
WO_850134_TV08021_SEP2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
12 in.
Upstream MH
08 0161
Downstream MH
08 0160
Dir. of Survey
Downstream
Length Surveyed
27.9 ft.
Total Length
27.9 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
4
O&M Quick
4200
O&M Rating
8
Overall Index
4
Overall Quick
Overall Rating
8
Pipe schematic from manhole 08 0161 to 08 0160
MH: 08 0161MH: 08 0160downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 01615 ft. MGO - General Observation - PIPE IS LINED27.8 ft. MCU - Camera Underwater27.8 ft. DAGS - Deposits Attached Grease, 25 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES27.9 ft. MSA - Survey Abandoned - CAM BLKD BY GREASE 25%

Observation photos (1)

  • Deposits Attached Grease, 25 %of cross sectional area, from 09 to 03 o'clock,  , within 8 inches of joint: YES

    27.8 ft. - Deposits Attached Grease, 25 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES

Observations (7)

DistanceCodeObservation
27.8MCU
0MWL
0MWM
0AMH08 0161
27.8DAGS
27.9MSACAM BLKD BY GREASE 25%
5MGOPIPE IS LINED

Properties (8)

additional_info
SC411964
custom_field_two
5
customer
1
datetime
2020-09-29T03:20:48-07:00
documentation
PROPIPE
is_lateral_inspection
false
lining
CIPP
year_laid
37424