Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 9, 2020, 11:10 AM
  • 04 0069_04 0068_11092020_044559.mp4

Date
11/09/2020
W/O
855012
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00415
PipeID
P11804
Time
3:10 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8184
Sewer Name
SHERMAN TRUNK
City
WEST HOLLYWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 04
Page No.
03
Purpose
Routine Assessment
Project
RFIR_WO_855012_TV04022_OCT2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
04 0069
Downstream MH
04 0068
Dir. of Survey
Downstream
Length Surveyed
290.5 ft.
Total Length
290.5 ft.
Structural Index
4
Structural Quick
5231
Structural Rating
13
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
13
Pipe schematic from manhole 04 0069 to 04 0068
MH: 04 0069MH: 04 0068downstream0 ft. MWM - Water Mark, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 04 00690 ft. MWL - Water Level, 5 %of cross sectional area2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start26.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"32 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"67 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"88.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"108.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"148.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"149.5 ft. HSV - Hole Soil Visible, at 01 o'clock, within 8 inches of joint: YES189.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"196.8 ft. TBA - Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"210.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"231 ft. HSV - Hole Soil Visible, at 12 o'clock, within 8 inches of joint: YES231.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"233.7 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"271.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"288.9 ft. MGO - General Observation - ROACHES IN MH288.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish290.5 ft. AMH - Downstream Manhole, Survey Ends - 04 0068290.5 ft. MGO - General Observation - CONNECTION AT MH 9 OCLOCK

Observation photos (4)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Hole Soil Visible, at 01 o'clock, within 8 inches of joint: YES

    149.5 ft. - Hole Soil Visible, at 01 o'clock, within 8 inches of joint: YES

  • Hole Soil Visible, at 12 o'clock, within 8 inches of joint: YES

    231 ft. - Hole Soil Visible, at 12 o'clock, within 8 inches of joint: YES

  • General Observation - ROACHES IN MH

    288.9 ft. - General Observation - ROACHES IN MH

Observations (22)

DistanceCodeObservation
149.5HSV
231HSV
148.7TFC
0MWM
290.5AMH04 0068
26.4TF
290.5MGOCONNECTION AT MH 9 OCLOCK
2CM
288.9MGOROACHES IN MH
271.8TFC
288.9CM
88.6TFC
196.8TBA
0AMH04 0069
67TF
210.3TFC
32TBA
189.1TFC
108.6TFC
233.7TBA
0MWL
231.4TFC

Properties (7)

additional_info
6301109200069A1
custom_field_three
HOLES
custom_field_two
2
customer
1
datetime
2020-11-09T03:10:33-08:00
documentation
PRO PIPE
is_lateral_inspection
false