Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 16, 2020, 04:53 AM
  • G 0094_E 0020_09152020_220601.mp4

Date
09/15/2020
W/O
849561
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00027
PipeID
P07607
Time
9:53 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8035
Sewer Name
JOINT OUTFALL E - UNIT 1
City
COMPTON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
20
Purpose
Routine Assessment
Project
RFIR_WO_849561_TV30031_SEP2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
42 in.
Width
15 in.
Upstream MH
G 0094
Downstream MH
E 0020
Dir. of Survey
Downstream
Length Surveyed
23.6 ft.
Total Length
23.6 ft.
Structural Index
4
Structural Quick
5131
Structural Rating
8
O&M Index
3
O&M Quick
3100
O&M Rating
3
Overall Index
4
Overall Quick
Overall Rating
11
Pipe schematic from manhole G 0094 to E 0020
MH: G 0094MH: E 0020downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 5 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - G 00942.1 ft. DSZ - Deposits Settled Other, 20 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start2.4 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start23.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish23.6 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish23.6 ft. MSA - Survey Abandoned - CAM BLKD BY DEBRIS/SLUDGE 20%23.6 ft. DSZ - Deposits Settled Other, 20 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish

Observation photos (3)

  • Deposits Settled Other,  20 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2.1 ft. - Deposits Settled Other, 20 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.4 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.4 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
0MWM
2.1DSZ
23.6SAP
23.6SRV
0MWL
0MGOCONNECTION AT MH 5 O'CLOCK
23.6MSACAM BLKD BY DEBRIS/SLUDGE 20%
0AMHG 0094
23.6DSZ
2.4SRV
2.4SAP

Properties (7)

additional_info
SC411848
custom_field_three
AGGREGATE PROJECTING/REINFORCEMET VISIBLE
custom_field_two
5
customer
1
datetime
2020-09-15T21:53:55-07:00
documentation
PROPIPE
is_lateral_inspection
false