Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 29, 2020, 07:59 AM
  • 14 0209_14 0208_10292020_011438.mp4

Date
10/29/2020
W/O
850059
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00584
PipeID
P18248
Time
12:59 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8175
Sewer Name
WEST SIDE TRUNK
City
LANCASTER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
18
Purpose
Routine Assessment
Project
RFIR_WO_850059_TV14035_SEP2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
14 0209
Downstream MH
14 0208
Dir. of Survey
Downstream
Length Surveyed
228.5 ft.
Total Length
228.5 ft.
Structural Index
3
Structural Quick
4C3D
Structural Rating
155
O&M Index
2
O&M Quick
412H
O&M Rating
94
Overall Index
3
Overall Quick
Overall Rating
249
Pipe schematic from manhole 14 0209 to 14 0208
MH: 14 0209MH: 14 0208downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 14 02090 ft. MGO - General Observation - CONNECTION AT MH, 3 AND 9 O'CLOCK2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start6.1 ft. CM - Crack Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES9.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start71.1 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"77.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"126.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"128.1 ft. FM - Fracture Multiple, from 01 to 05 o'clock, within 8 inches of joint: YES129.5 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"131 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start131 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish185.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"188.4 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"226.8 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish226.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish228.5 ft. AMH - Downstream Manhole, Survey Ends - 14 0208

Observation photos (5)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES

    6.1 ft. - Crack Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    9.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 01 to 05 o'clock, within 8 inches of joint: YES

    128.1 ft. - Fracture Multiple, from 01 to 05 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    131 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (19)

DistanceCodeObservation
226.8FM
6.1CM
131FM
0MWM
228.5AMH14 0208
188.4TFA
0MWL
226.8DAGS
131CM
126.8TFA
9.2CM
129.5TFA
2DAGS
0AMH14 0209
0MGOCONNECTION AT MH, 3 AND 9 O'CLOCK
77.3TFA
185.8TFA
71.1TFA
128.1FM

Properties (5)

custom_field_two
3
customer
1
datetime
2020-10-29T00:59:18-07:00
documentation
PRO PIPE
is_lateral_inspection
false