Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 16, 2020, 04:29 AM
  • 02 0853_02 0852 _10152020_214442.mp4

Date
10/15/2020
W/O
850047
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00297
PipeID
P03420
Time
9:29 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8124
Sewer Name
OLD RIVER SCHOOL ROAD RELIEF TRUNK, SECTS 2&3
City
DOWNEY
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
26
Purpose
Routine Assessment
Project
RFIR_WO_850047_TV02269_SEP2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
33 in.
Width
15 in.
Upstream MH
02 0853
Downstream MH
02 0852
Dir. of Survey
Downstream
Length Surveyed
9.3 ft.
Total Length
9.3 ft.
Structural Index
4
Structural Quick
5131
Structural Rating
8
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
8
Pipe schematic from manhole 02 0853 to 02 0852
MH: 02 0853MH: 02 0852downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 08530 ft. MWL - Water Level, 15 %of cross sectional area2 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK2 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK2.1 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start9.3 ft. AMH - Downstream Manhole, Survey Ends - 02 08529.3 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish9.3 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK9.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (2)

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
2.1SRV
9.3AMH02 0852
2MGOACTIVE CONNECTION AT MH 9 O'CLOCK
2.1SAP
0MWM
9.3SRV
0AMH02 0853
2MGOACTIVE CONNECTION AT MH 3 O'CLOCK
9.3MGOACTIVE CONNECTION AT MH 3 O'CLOCK
0MWL
9.3SAP

Properties (7)

additional_info
6301015200075P1
custom_field_three
AGGREGATE PROJECTING/REINFORCEMENT VISIBLE
custom_field_two
2
customer
1
datetime
2020-10-15T21:29:48-07:00
documentation
PROPIPE
is_lateral_inspection
false