Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 10, 2020, 11:18 AM
  • B 0477_B 0476_11102020_035042.mp4

Date
11/10/2020
W/O
0860172
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00094
PipeID
P09002
Time
3:18 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1621R
Sewer Name
B JOINT OUTFALL B - UNIT 5D
City
PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
06
Purpose
Maintenance Related
Project
20201110MDM_JOINT_OUTFALL_B_UNIT_5D
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
B 0476
Downstream MH
B 0477
Dir. of Survey
Upstream
Length Surveyed
265.6 ft.
Total Length
265.6 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
4133
O&M Rating
18
Overall Index
2
Overall Quick
Overall Rating
18
Pipe schematic from manhole B 0476 to B 0477
MH: B 0476MH: B 0477upstream0 ft. AMH - Upstream Manhole, Survey Ends - 4:30AM26.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped29.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped35.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open44.9 ft. RMJ - Roots Medium Joint, from 01 to 04 o'clock, 10 %, within 8 inches of joint: YESR86.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped89.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped98.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Active98.6 ft. RFJ - Roots Fine Joint, from 09 to 11 o'clock, within 8 inches of joint: YESR - 4%141.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open141.1 ft. RMC - Roots Medium Connection, from 02 to 04 o'clock, 10 %, within 8 inches of joint: YES147.2 ft. RFJ - Roots Fine Joint, at 03 o'clock, within 8 inches of joint: YESR - 4%147.2 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Capped154 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open154 ft. RFC - Roots Fine Connection, from 09 to 11 o'clock, within 8 inches of joint: YES - 2%157.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped178.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open189.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open195.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped240.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open249.5 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open-70% ROOTS249.6 ft. RMC - Roots Medium Connection, from 01 to 05 o'clock, 5 %, within 8 inches of joint: YES265.6 ft. MWL - Water Level, 15 %of cross sectional area265.6 ft. MWM - Water Mark, 50 %of cross sectional area265.6 ft. AMH - Upstream Manhole, Survey Begins - 4:05AM

Observations (25)

DistanceCodeObservation
111.6TFOpen
229.8TFOpen
118.4RFJ4%
70.4TFCCapped
178.9TFCCapped
124.5TFOpen
0MWL
111.6RFC2%
236.5TFCCapped
118.4TFCCapped
167TFAActive
108.2TFCCapped
167RFJ4%
124.5RMC
176.3TFCCapped
239.5TFCCapped
87.5TFOpen
24.9TFOpen
16RMC
265.6AMH4:30AM
0MWM
0AMH4:05AM
220.7RMJ
76.5TFOpen
16.1TFDOpen-70% ROOTS

Properties (5)

additional_info
ROOT EVALUATION ONLY
customer
LACSD
datetime
2020-11-10T03:18:39-08:00
documentation
MARTIN,OLIVER 111,CASTILLO,RUVALCABA
is_lateral_inspection
false