Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 20, 2020, 07:45 AM
  • 16 0278_16 0277_10202020_005553.mp4

Date
10/20/2020
W/O
849553
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00654
PipeID
P13326
Time
12:45 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
KK8130
Sewer Name
CHAPEL AVENUE TRUNK, SECTION 3
City
SOUTH PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
17
Purpose
Routine Assessment
Project
WO_849553_TV16076_SEP2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
16 0278
Downstream MH
16 0277
Dir. of Survey
Downstream
Length Surveyed
329 ft.
Total Length
329 ft.
Structural Index
2
Structural Quick
3111
Structural Rating
4
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
4
Pipe schematic from manhole 16 0278 to 16 0277
MH: 16 0278MH: 16 0277downstream0 ft. AMH - Upstream Manhole, Survey Begins - 16 02780 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area4.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start104.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"140.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"158.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"223.7 ft. CC - Crack Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES329 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish329 ft. AMH - Downstream Manhole, Survey Ends - 16 0277

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.3 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES

    223.7 ft. - Crack Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES

Observations (10)

DistanceCodeObservation
0AMH16 0278
223.7CC
104.9TF
0MWM
4.3SAV
140.2TF
0MWL
329SAV
329AMH16 0277
158.8TF

Properties (7)

additional_info
6301019200075P3
custom_field_three
AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2020-10-20T00:45:36-07:00
documentation
PROPIPE
is_lateral_inspection
false