Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 5, 2020, 10:58 AM
  • 16 0062_16 0061_10052020_041531.mp4

Date
10/05/2020
W/O
849888
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00639
PipeID
P13076
Time
3:58 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8156
Sewer Name
ALLEN AVENUE TRUNK, SECTS 1,2,&4
City
SAN MARINO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
18
Purpose
Routine Assessment
Project
RFIR_WO_849888_TV16113_SEP2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
16 0062
Downstream MH
16 0061
Dir. of Survey
Downstream
Length Surveyed
387.1 ft.
Total Length
387.1 ft.
Structural Index
2
Structural Quick
5131
Structural Rating
178
O&M Index
2
O&M Quick
312N
O&M Rating
157
Overall Index
2
Overall Quick
Overall Rating
335
Pipe schematic from manhole 16 0062 to 16 0061
MH: 16 0062MH: 16 0061downstream0 ft. AMH - Upstream Manhole, Survey Begins - 16 00620 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start226.3 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES227.5 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start252 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES263.5 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish298.6 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"373 ft. TBD - Tap Break-In Defective, at 02 o'clock, -, , within 8 inches of joint: YES, 4", 6" - CONN BROKEN/ACTIVE373 ft. HSV - Hole Soil Visible, at 02 o'clock, within 8 inches of joint: YES, 4ft - SEPARATED CONNECTION384.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish385 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish387.1 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/387.1 ft. AMH - Downstream Manhole, Survey Ends - 16 0061

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    226.3 ft. - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    227.5 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    252 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

Observations (16)

DistanceCodeObservation
2SSS
0AMH16 0062
373TBDCONN BROKEN/ACTIVE
252CL
385SSS
387.1MGOCONN @ MH 9 O'CLOCK/
298.6TBA
2DAGS
0MWM
263.5CL
0MWL
226.3CM
227.5CL
387.1AMH16 0061
384.9DAGS
373HSVSEPARATED CONNECTION

Properties (7)

additional_info
6301005200098P2
custom_field_three
MULTIPLE CRACKS
custom_field_two
2
customer
1
datetime
2020-10-05T03:58:30-07:00
documentation
PRO PIPE
is_lateral_inspection
false