Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 19, 2020, 11:48 AM
  • 16 0048_16 0047_10192020_045532.mp4

Date
10/19/2020
W/O
849888
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00639
PipeID
P13061
Time
4:48 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8127
Sewer Name
ALLEN AVENUE TRUNK, SECTS 1,2,&4
City
SAN GABRIEL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
01
Purpose
Routine Assessment
Project
RFIR_WO_849888_TV16113_SEP2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
16 in.
Width
16 in.
Upstream MH
16 0048
Downstream MH
16 0047
Dir. of Survey
Downstream
Length Surveyed
269.6 ft.
Total Length
269.6 ft.
Structural Index
3
Structural Quick
3J2J
Structural Rating
265
O&M Index
2
O&M Quick
2J00
O&M Rating
106
Overall Index
2
Overall Quick
Overall Rating
371
Pipe schematic from manhole 16 0048 to 16 0047
MH: 16 0048MH: 16 0047downstream0 ft. MGO - General Observation - ROACHES @ MH0 ft. AMH - Upstream Manhole, Survey Begins - 16 00480 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 10 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start4.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start267 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish267 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish269 ft. MGO - General Observation - ROACHES @ MH269.6 ft. AMH - Downstream Manhole, Survey Ends - 16 0047269.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
269.6AMH16 0047
4.2CM
2SSS
0MGOROACHES @ MH
267DAGS
2DAGS
267SSS
0AMH16 0048
0MWL
269.6CM
0MWM
269MGOROACHES @ MH

Properties (7)

additional_info
6301019200075A1
custom_field_three
SPALLING
custom_field_two
3
customer
1
datetime
2020-10-19T04:48:35-07:00
documentation
PROPIPE
is_lateral_inspection
false