Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 19, 2020, 09:47 AM
  • 16 0046_16 0045_10192020_030316.mp4

Date
10/19/2020
W/O
849888
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00639
PipeID
P13059
Time
2:47 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8127
Sewer Name
ALLEN AVENUE TRUNK, SECTS 1,2,&4
City
SAN GABRIEL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
01
Purpose
Routine Assessment
Project
RFIR_WO_849888_TV16113_SEP2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
16 in.
Width
16 in.
Upstream MH
16 0045
Downstream MH
16 0046
Dir. of Survey
Upstream
Length Surveyed
466.6 ft.
Total Length
466.6 ft.
Structural Index
3
Structural Quick
3R2Q
Structural Rating
463
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
467
Pipe schematic from manhole 16 0045 to 16 0046
MH: 16 0045MH: 16 0046upstream0 ft. AMH - Upstream Manhole, Survey Ends - 16 00460 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0.6 ft. MGO - General Observation - ROACHES @ MH2.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish2.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish464.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start464.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start464.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start466.6 ft. MWL - Water Level, 5 %of cross sectional area466.6 ft. MGO - General Observation - ROACHES @ MH466.6 ft. AMH - Downstream Manhole, Survey Begins - 16 0045466.6 ft. MWM - Water Mark, 10 %of cross sectional area

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
0MWL
2.3CM
464DAGS
464SSS
0MGOROACHES @ MH
466.6AMH16 0046
2DAGS
0AMH16 0045
2SSS
0MWM
466.6CM
466MGOROACHES @ MH

Properties (7)

additional_info
6301019200075A1
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2020-10-19T02:47:51-07:00
documentation
PROPIPE
is_lateral_inspection
false