Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 19, 2020, 10:34 AM
  • 16 0045_16 0044_10192020_034326.mp4

Date
10/19/2020
W/O
849888
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00639
PipeID
P13058
Time
3:34 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8127
Sewer Name
ALLEN AVENUE TRUNK, SECTS 1,2,&4
City
SAN GABRIEL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
01
Purpose
Routine Assessment
Project
RFIR_WO_849888_TV16113_SEP2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
16 in.
Width
16 in.
Upstream MH
16 0045
Downstream MH
16 0044
Dir. of Survey
Downstream
Length Surveyed
344.2 ft.
Total Length
344.2 ft.
Structural Index
3
Structural Quick
3M2M
Structural Rating
340
O&M Index
2
O&M Quick
2M00
O&M Rating
136
Overall Index
2
Overall Quick
Overall Rating
476
Pipe schematic from manhole 16 0045 to 16 0044
MH: 16 0045MH: 16 0044downstream0 ft. AMH - Upstream Manhole, Survey Begins - 16 00450 ft. MGO - General Observation - ROACHES @ MH0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 10 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start342 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish342 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish344 ft. MGO - General Observation - ROACHES @ MH344.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish344.2 ft. AMH - Downstream Manhole, Survey Ends - 16 0044

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
342DAGS
2SSS
344.2CM
0AMH16 0045
0MGOROACHES @ MH
2CM
344.2AMH16 0044
0MWL
344MGOROACHES @ MH
342SSS
2DAGS
0MWM

Properties (7)

additional_info
6301019200075A1
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2020-10-19T03:34:53-07:00
documentation
PROPIPE
is_lateral_inspection
false