Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 14, 2020, 05:36 AM
  • 22 0916_22 0915_10132020_225042.mp4

Date
10/13/2020
W/O
849555
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00799
PipeID
P17287
Time
10:36 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8159
Sewer Name
CONEY TRUNK, SECTS 2&3
City
AZUSA
Loc. details
Parking Lot
Location Code
G
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
11
Purpose
Routine Assessment
Project
RFIR_WO_849555_TV22104_SEP2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
22 0916
Downstream MH
22 0915
Dir. of Survey
Downstream
Length Surveyed
316.3 ft.
Total Length
316.3 ft.
Structural Index
3
Structural Quick
3L2K
Structural Rating
313
O&M Index
2
O&M Quick
2L00
O&M Rating
126
Overall Index
2
Overall Quick
Overall Rating
439
Pipe schematic from manhole 22 0916 to 22 0915
MH: 22 0916MH: 22 0915downstream0 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/UNKNOWN0 ft. MGO - General Observation - ROACHES @ MH0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 22 09160 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start12.6 ft. MGO - General Observation - 65% MAG COAT45.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"56 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN.071.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"96.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"128.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"153.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"314 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish314.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish314.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish316.3 ft. MGO - General Observation - ROACHES @ MH316.3 ft. AMH - Downstream Manhole, Survey Ends - 22 0915

Observation photos (5)

  • General Observation - ROACHES @ MH

    0 ft. - General Observation - ROACHES @ MH

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - 65% MAG COAT

    12.6 ft. - General Observation - 65% MAG COAT

  • General Observation - ROACHES @ MH

    316.3 ft. - General Observation - ROACHES @ MH

Observations (20)

DistanceCodeObservation
96.2TFC
2DAGS
56TFOPEN.0
0MGOCONN @ MH 9 O'CLOCK/UNKNOWN
314SSS
314.5SAV
2SAV
0MGOROACHES @ MH
128.9TFC
0MWL
71.4TFC
153.4TFC
316.3MGOROACHES @ MH
2SSS
12.6MGO65% MAG COAT
316.3AMH22 0915
0AMH22 0916
0MWM
45.3TFC
314.5DAGS

Properties (7)

additional_info
69301013200138P1
custom_field_three
VISIBLE AGGREGATE
custom_field_two
3
customer
1
datetime
2020-10-13T22:36:13-07:00
documentation
PRO PIPE
is_lateral_inspection
false