Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 23, 2020, 03:53 PM
  • 21 0325_21 0324_10232020_090358.mp4

Date
10/23/2020
W/O
849681
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00763
PipeID
P15522
Time
8:53 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8135
Sewer Name
DISTRICT #21 OUTFALL TRUNK
City
Pomona
Loc. details
Parking Lot
Location Code
G
Use of Sewer
Sanitary Sewer
District
District 21
Page No.
14
Purpose
Routine Assessment
Project
RFIR_WO_849681_TV21101_SEP2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Width
27 in.
Upstream MH
21 0325
Downstream MH
21 0324
Dir. of Survey
Downstream
Length Surveyed
61.6 ft.
Total Length
61.6 ft.
Structural Index
4
Structural Quick
5131
Structural Rating
8
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
8
Pipe schematic from manhole 21 0325 to 21 0324
MH: 21 0325MH: 21 0324downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 21 03252.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3.2 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start61.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish61.6 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish61.6 ft. AMH - Downstream Manhole, Survey Ends - 21 0324

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.2 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
61.6SRV
0MWM
0MWL
2.1SAP
0MGOCONNECTION AT MH 9 O'CLOCK
61.5SAP
3.2SRV
0AMH21 0325
61.6AMH21 0324

Properties (7)

additional_info
6301023200075A2
custom_field_three
AGGREGATE PROJECTING/ REINFORCEMENT VISIBLE
custom_field_two
2
customer
1
datetime
2020-10-23T08:53:56-07:00
documentation
ProPipe
is_lateral_inspection
false