Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 5, 2020, 10:27 AM
  • 14 1109_14 1108_11052020_023821.mp4

Date
11/05/2020
W/O
850046
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z01179
PipeID
P26061
Time
2:27 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8182
Sewer Name
WEST SIDE RELIEF TRUNK
City
LANCASTER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
10
Purpose
Routine Assessment
Project
WO_850046_TV14056_SEP2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
14 1109
Downstream MH
14 1108
Dir. of Survey
Downstream
Length Surveyed
253.4 ft.
Total Length
253.4 ft.
Structural Index
2
Structural Quick
2I00
Structural Rating
100
O&M Index
2
O&M Quick
2I00
O&M Rating
100
Overall Index
2
Overall Quick
Overall Rating
200
Pipe schematic from manhole 14 1109 to 14 1108
MH: 14 1109MH: 14 1108downstream0 ft. AMH - Upstream Manhole, Survey Begins - 14 11090 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start31.6 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: YES, 6"36.2 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"81.5 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: YES, 6"84.5 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"144.2 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: YES, 6"182.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"208.3 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"228.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"251 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish251.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish253.4 ft. AMH - Downstream Manhole, Survey Ends - 14 1108

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (16)

DistanceCodeObservation
84.5TFA
208.3TFA
81.5TFA
251SSS
228.7TFA
0AMH14 1109
0MWM
253.4AMH14 1108
144.2TFA
182.9TFA
31.6TFA
2DAGS
2SSS
36.2TFA
251.5DAGS
0MWL

Properties (8)

additional_info
6301104200138P2
custom_field_three
LIGHT GREASE/SPALLING
custom_field_two
3
customer
1
datetime
2020-11-05T02:27:00-08:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
40175