Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 6, 2020, 09:39 AM
  • 14 1108_14 1107_11062020_020031.mp4

Date
11/06/2020
W/O
850046
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z01179
PipeID
P26060
Time
1:39 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8183
Sewer Name
WEST SIDE RELIEF TRUNK
City
LANCASTER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
10
Purpose
Routine Assessment
Project
WO_850046_TV14056_SEP2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
14 1108
Downstream MH
14 1107
Dir. of Survey
Downstream
Length Surveyed
392 ft.
Total Length
392 ft.
Structural Index
2
Structural Quick
2N00
Structural Rating
154
O&M Index
2
O&M Quick
2]00
O&M Rating
298
Overall Index
2
Overall Quick
Overall Rating
452
Pipe schematic from manhole 14 1108 to 14 1107
MH: 14 1108MH: 14 1107downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 14 11080 ft. MWL - Water Level, 20 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start19.1 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"34.1 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start - MINERAL DEPOSITS70.7 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"75 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"119 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"124.5 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"170.3 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: YES, 6"172.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"271 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"275.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"321.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"324 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"389 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish389.7 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Finish389.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish392 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE392 ft. AMH - Downstream Manhole, Survey Ends - 14 1107392 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock,  , within 8 inches of joint: YES, Start - MINERAL DEPOSITS

    34.1 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start - MINERAL DEPOSITS

Observations (23)

DistanceCodeObservation
34.1DAEMINERAL DEPOSITS
19.1TFA
2DAGS
389.7DAE
2SSS
321.2TFA
170.3TFA
70.7TFA
392MGOCONN @ MH 9 O'CLOCK/ACTIVE
0MWM
392AMH14 1107
271TFA
119TFA
75TFA
389.7DAGS
392MGOCONN @ MH 3 O'CLOCK/ACTIVE
0AMH14 1108
0MWL
324TFA
124.5TFA
172.3TFA
389SSS
275.7TFA

Properties (8)

additional_info
6301105200138P1
custom_field_three
LIGHT GREASE/SPALLING
custom_field_two
3
customer
1
datetime
2020-11-06T01:39:19-08:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
40175