Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 6, 2020, 10:17 AM
  • 14 1106_14 1105_11062020_023730.mp4

Date
11/06/2020
W/O
850046
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z01179
PipeID
P26058
Time
2:17 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8183
Sewer Name
WEST SIDE RELIEF TRUNK
City
LANCASTER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
10
Purpose
Routine Assessment
Project
WO_850046_TV14056_SEP2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
14 1106
Downstream MH
14 1105
Dir. of Survey
Downstream
Length Surveyed
329.9 ft.
Total Length
329.9 ft.
Structural Index
2
Structural Quick
2L00
Structural Rating
130
O&M Index
2
O&M Quick
2Y00
O&M Rating
260
Overall Index
2
Overall Quick
Overall Rating
390
Pipe schematic from manhole 14 1106 to 14 1105
MH: 14 1106MH: 14 1105downstream0 ft. AMH - Upstream Manhole, Survey Begins - 14 11060 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area2 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start67.6 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: YES, 6"117.3 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: YES, 6"121.1 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"169.6 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"211.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"215.2 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"263.1 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"311 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"314.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"327 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish328.1 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish328.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish329.9 ft. AMH - Downstream Manhole, Survey Ends - 14 1105

Observation photos (2)

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (19)

DistanceCodeObservation
328.1DAE
121.1TFA
311TFA
2DAE
329.9AMH14 1105
215.2TFA
327SSS
2SSS
328.1DAGS
263.1TFA
67.6TFA
117.3TFA
211.3TFA
0AMH14 1106
0MWM
2DAGS
0MWL
169.6TFA
314.9TFA

Properties (8)

additional_info
6301105200138P1
custom_field_three
LIGHT GREASE/SPALLING
custom_field_two
3
customer
1
datetime
2020-11-06T02:17:21-08:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
40175