Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 24, 2020, 09:00 AM
  • 14 1096_14 1095_09242020_011623.mp4

Date
09/24/2020
W/O
850046
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z01179
PipeID
P26048
Time
2:00 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8152
Sewer Name
WEST SIDE RELIEF TRUNK
City
LANCASTER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
05
Purpose
Routine Assessment
Project
WO_850046_TV14056_SEP2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
27 in.
Width
27 in.
Upstream MH
14 1096
Downstream MH
14 1095
Dir. of Survey
Downstream
Length Surveyed
388.8 ft.
Total Length
388.8 ft.
Structural Index
2
Structural Quick
2N00
Structural Rating
154
O&M Index
2
O&M Quick
2N00
O&M Rating
154
Overall Index
2
Overall Quick
Overall Rating
308
Pipe schematic from manhole 14 1096 to 14 1095
MH: 14 1096MH: 14 1095downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 14 10960 ft. MWL - Water Level, 15 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start20.8 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 4", 4" - OPEN27.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN43.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN116.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN123.1 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN171 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN200.1 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"225.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"228.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"267.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN386 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish386.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish388.8 ft. AMH - Downstream Manhole, Survey Ends - 14 1095

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (18)

DistanceCodeObservation
0MWM
228.3TFA
388.8AMH14 1095
0AMH14 1096
171TFOPEN
386SSS
2DAGS
20.8TFOPEN
225.6TFA
386.8DAGS
0MWL
116.3TFOPEN
123.1TFOPEN
43.8TFOPEN
2SSS
27.3TFOPEN
267.2TFOPEN
200.1TFA

Properties (8)

additional_info
SC411895
custom_field_three
LIGHT GREASE/SPALLING
custom_field_two
3
customer
1
datetime
2020-09-24T02:00:02-07:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
40175