Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 15, 2020, 08:48 AM
  • A 1202_A 1201 _10152020_020526.mp4

Date
10/15/2020
W/O
849615
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00973
PipeID
P02850
Time
1:48 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8123
Sewer Name
JOINT OUTFALL A - UNIT 9
City
BELL GARDENS
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
20
Purpose
Routine Assessment
Project
RFIR_WO_849615_TV02207_SEP2020
Sewer Type
Gravity
Material
RCP-CTL
Shape
Circular
Height
39 in.
Width
15 in.
Upstream MH
A 1202
Downstream MH
A 1201
Dir. of Survey
Downstream
Length Surveyed
295.8 ft.
Total Length
295.8 ft.
Structural Index
4
Structural Quick
5141
Structural Rating
12
O&M Index
3
O&M Quick
3100
O&M Rating
3
Overall Index
4
Overall Quick
Overall Rating
15
Pipe schematic from manhole A 1202 to A 1201
MH: A 1202MH: A 1201downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - A 12022.1 ft. MB - Missing Brick, from 08 to 04 o'clock, Start - TILES2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. DSZ - Deposits Settled Other, 20 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Start - SLUDGE/DEBRIS190 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start295.7 ft. DSZ - Deposits Settled Other, 20 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Finish295.8 ft. MB - Missing Brick, from 08 to 04 o'clock, Finish295.8 ft. MSA - Survey Abandoned - CAM BLKD BY DEBRIS 25%295.8 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish295.8 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish

Observation photos (3)

  • Missing Brick, from 08 to 04 o'clock, Start - TILES

    2.1 ft. - Missing Brick, from 08 to 04 o'clock, Start - TILES

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    190 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
295.8MB
295.8MSACAM BLKD BY DEBRIS 25%
295.7DSZ
295.8SAP
0MWM
2.1MBTILES
2.1SAP
0MWL
190SRV
295.8SRV
0AMHA 1202
2.1DSZSLUDGE/DEBRIS

Properties (6)

additional_info
6301014200075P3
custom_field_two
5
customer
1
datetime
2020-10-15T01:48:08-07:00
documentation
PROPIPE
is_lateral_inspection
false