Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 4, 2020, 09:22 AM
  • 02 0927_02 0926_1142020_050929.mp4

Date
11/04/2020
W/O
0855066
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00252
PipeID
P03495
Time
1:22 AM
Certificate
U-101406022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1615
Sewer Name
02 DOWNEY-BELLFLOWER DIVERSION TRUNK
City
DOWNEY
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
27
Purpose
Capital Improvement Program Assesment
Project
20201104MDM_DOWNEY_BELLFLOWER_DIVERSION_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Upstream MH
02 0927
Downstream MH
02 0926
Dir. of Survey
Downstream
Length Surveyed
349.9 ft.
Total Length
349.9 ft.
Structural Index
3
Structural Quick
513B
Structural Rating
86
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
90
Pipe schematic from manhole 02 0927 to 02 0926
MH: 02 0927MH: 02 0926downstream0 ft. AMH - Upstream Manhole, Survey Begins - 5:10AM0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area7 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - H11.5 ft. FC - Fracture Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES - HAIRLINE11.5 ft. FL - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES, Start - HAIRLINE16.6 ft. FL - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES, Finish - H22.5 ft. FC - Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES - H27.5 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - H32.2 ft. FL - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES - H36.9 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H42.6 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - H47.4 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - H52.8 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - H62.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - SLIGHT77.8 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H108.7 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H118.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - H124.2 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H128.8 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H150.2 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H155 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - SL170.2 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - H206.5 ft. FC - Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES - H221.1 ft. SMW - Surface Missing Wall, at 02 o'clock, within 8 inches of joint: YES - SMALL CHIP OUT221.1 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - H252.5 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - H267.2 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - H278.1 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - H286.3 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - H287 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - H288 ft. FL - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES - H288 ft. FC - Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES - H298.3 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H303.2 ft. FC - Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES - H328.7 ft. FC - Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES - SLIGHT328.7 ft. FC - Fracture Circumferential, from 10 to 11 o'clock, within 8 inches of joint: YES - H338.6 ft. FC - Fracture Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES - H338.6 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H346.3 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - H349.9 ft. AMH - Downstream Manhole, Survey Ends - 9:40AM

Observation photos (1)

  • Surface Missing Wall, at 02 o'clock, within 8 inches of joint: YES - SMALL CHIP OUT

    221.1 ft. - Surface Missing Wall, at 02 o'clock, within 8 inches of joint: YES - SMALL CHIP OUT

Observations (41)

DistanceCodeObservation
221.1SMWSMALL CHIP OUT
0AMH5:10AM
349.9AMH9:40AM
36.9FLH
328.7FCSLIGHT
118.4FLH
288FLH
267.2FLH
338.6FCH
0MWM
47.4FLH
252.5FLH
27.5FLH
328.7FCH
32.2FLH
11.5FCHAIRLINE
62.4FLSLIGHT
128.8FLH
303.2FCH
338.6FLH
155FCSL
346.3FLH
0MWL
7FCH
170.2FLH
108.7FLH
286.3FCH
150.2FCH
221.1FCH
298.3FLH
124.2FLH
52.8FLH
42.6FLH
278.1FCH
22.5FCH
77.8FLH
287FCH
206.5FCH
11.5FLHAIRLINE
16.6FLH
288FCH

Properties (6)

custom_field_three
HAIRLINE FRACTURE JOINT TO JOINT LONGER
custom_field_two
2
customer
LACSD
datetime
2020-11-04T01:22:48-08:00
documentation
MARTIN,OLIVER 111,RUVALCABA
is_lateral_inspection
false