Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 20, 2020, 09:11 AM
  • B 1261_B 1260_10202020_022020.mp4

Date
10/20/2020
W/O
849676
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z01127
PipeID
P13711
Time
2:11 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8131
Sewer Name
JOINT OUTFALL B - UNIT 6H RELIEF
City
SOUTH PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
20
Purpose
Routine Assessment
Project
WO_849676_TV16048_SEP2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
B 1261
Downstream MH
B 1260
Dir. of Survey
Downstream
Length Surveyed
402.2 ft.
Total Length
402.2 ft.
Structural Index
2
Structural Quick
2O00
Structural Rating
160
O&M Index
2
O&M Quick
2O00
O&M Rating
160
Overall Index
2
Overall Quick
Overall Rating
320
Pipe schematic from manhole B 1261 to B 1260
MH: B 1261MH: B 1260downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 12610 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - ROACHES @ MH2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start400 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish400 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish402 ft. MGO - General Observation - ROACHES @ MH402.2 ft. AMH - Downstream Manhole, Survey Ends - B 1260

Observations (10)

DistanceCodeObservation
402.2AMHB 1260
2DAGS
402MGOROACHES @ MH
0MWL
0AMHB 1261
0MWM
0MGOROACHES @ MH
2SSS
400DAGS
400SSS

Properties (8)

additional_info
6301019200075P4
custom_field_three
NO SEVERE DEFECTS/SPALLING
custom_field_two
3
customer
1
datetime
2020-10-20T02:11:44-07:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
28103