Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 29, 2020, 03:53 PM
  • H 0647_H 0646_10292020_091144.mp4

Date
10/29/2020
W/O
0855057
Weather
Dry
Operator/Surveyor
SANTIAGO OBREGON
Sewer ID
Z00192
PipeID
P11053
Time
8:53 AM
Certificate
U1014-06022541
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1606
Sewer Name
H JOINT OUTFALL H - UNIT 8J
City
WEST COVINA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
24
Purpose
Capital Improvement Program Assesment
Project
20201029SHO_JOINT_OUTFALL_H_UNIT_8J
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
H 0647
Downstream MH
H 0646
Dir. of Survey
Downstream
Length Surveyed
340.7 ft.
Total Length
340.7 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole H 0647 to H 0646
MH: H 0647MH: H 0646downstream0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 06470 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MGO - General Observation - CONNECTION IN MH @ 311 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start11 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start11 ft. MGO - General Observation - 15% MAG COAT INTACT51.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"55.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"101.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"145.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"170 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"203.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"288.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"308.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"338.5 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish338.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish340.7 ft. AMH - Downstream Manhole, Survey Ends - H 0646

Observations (18)

DistanceCodeObservation
11SSS
55.8TF
340.7AMHH 0646
338.5SSS
170TFC
0MWL
308.6TF
203.3TF
51.9TFC
101.1TF
11SAV
145.3TFC
0AMHH 0647
0MWM
0MGOCONNECTION IN MH @ 3
288.3TF
11MGO15% MAG COAT INTACT
338.5SAV

Properties (7)

additional_info
RFIR
custom_field_three
MINOR SPALLING
custom_field_two
2
customer
LACSD
datetime
2020-10-29T08:53:20-07:00
documentation
OBREGON, SHADLER, RAMIREZ, BRAR
is_lateral_inspection
false