Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 3, 2020, 07:21 PM
  • 3_1_1_03112020_112509.mp4

Date
11/03/2020
W/O
0860426
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00594
PipeID
P12635
Time
11:21 AM
Certificate
U-415-06024039
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0356
Sewer Name
ARCADIA-SIERRA MADRE TRUNK, SECTS 3&2A
City
SIERRA MADRE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
01
Purpose
Maintenance Related
Project
20201103DF_ARCADIA_SIERRA_MADRE_TRUNK_SECTS_3_2A
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
10 in.
Upstream MH
15 0857
Downstream MH
15 0856
Dir. of Survey
Downstream
Length Surveyed
314.5 ft.
Total Length
314.5 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2K00
O&M Rating
124
Overall Index
2
Overall Quick
Overall Rating
124
Pipe schematic from manhole 15 0857 to 15 0856
MH: 15 0857MH: 15 0856downstream0 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 11:22 AM2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start81.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4" - OPEN84.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4" - OPEN103.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4" - OPEN114.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"127.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"134.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"165.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4" - OPEN187.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4" - OPEN192.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4" - OPEN195.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"219.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4"246.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4" - OPEN270.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4" - OPEN311 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish314.5 ft. AMH - Downstream Manhole, Survey Ends - 11:56 AM314.5 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE

Observations (21)

DistanceCodeObservation
114.4TFA
192.6TFOPEN
0MGOCONN @ MH 9 O'CLOCK/ACTIVE
165.6TFOPEN
311DAGS
127.3TFA
0MWL
246.3TFOPEN
314.5AMH11:56 AM
2DAGS
195.7TFA
270.6TFOPEN
187.4TFOPEN
0MWM
314.5MGOCONN @ MH 9 O'CLOCK/ACTIVE
219.8TF
81.7TFOPEN
103.3TFOPEN
134.4TFA
0AMH11:22 AM
84.6TFOPEN

Properties (5)

custom_field_two
4
customer
1
datetime
2020-11-03T11:21:31-08:00
documentation
FRANKLIN, RAMIREZ, IGNACIO
is_lateral_inspection
false