Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 16, 2020, 09:55 AM
  • 22 0557_22 0556_10162020_030652.mp4

Date
10/16/2020
W/O
849889
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00791
PipeID
P16899
Time
2:55 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8162
Sewer Name
BEN LOMOND TRUNK
City
GLENDORA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_849889_TV22102_SEP2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
22 0557
Downstream MH
22 0556
Dir. of Survey
Downstream
Length Surveyed
263.5 ft.
Total Length
263.5 ft.
Structural Index
3
Structural Quick
3I00
Structural Rating
156
O&M Index
2
O&M Quick
2I00
O&M Rating
104
Overall Index
3
Overall Quick
Overall Rating
260
Pipe schematic from manhole 22 0557 to 22 0556
MH: 22 0557MH: 22 0556downstream0 ft. MGO - General Observation - ROACHES @ MH0 ft. AMH - Upstream Manhole, Survey Begins - 22 05570 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start48 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"57.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"99.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN196.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN201.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"262.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish262.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish263.5 ft. MGO - General Observation - ROACHES @ MH263.5 ft. AMH - Downstream Manhole, Survey Ends - 22 0556263.5 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE

Observation photos (4)

  • General Observation - ROACHES @ MH

    0 ft. - General Observation - ROACHES @ MH

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - ROACHES @ MH

    263.5 ft. - General Observation - ROACHES @ MH

Observations (17)

DistanceCodeObservation
263.5MGOROACHES @ MH
2SAP
99.6TFOPEN
0MGOROACHES @ MH
2DAGS
201.8TFC
48TFA
263.5AMH22 0556
263.5MGOCONN @ MH 3 O'CLOCK/ACTIVE
196.6TFOPEN
262.5DAGS
0AMH22 0557
0MWM
57.9TFC
0MWL
262.5SAP
0MGOCONN @ MH 3 O'CLOCK/ACTIVE

Properties (7)

additional_info
6301015200138P1
custom_field_three
PROJECTING AGGREGATE
custom_field_two
3
customer
1
datetime
2020-10-16T02:55:55-07:00
documentation
PRO PIPE
is_lateral_inspection
false